DX-LN3-016 269503 EATON ELECTRIC Main choke, AC, 3p, 16A, 1.84mH, 550V50/60Hz View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

DX-LN3-016 269503 EATON ELECTRIC Main choke, AC, 3p, 16A, 1.84mH, 550V50/60Hz

DX-LN3-016

269503

EATON-MOELLER

Main choke, AC, 3p, 16A, 1.84mH, 550V50/60Hz

DX-LN3-016

Main choke, three-phase, 550 V + 0% (50/60 Hz), V AC, 16 A, 1.84 mH

More details


Low-voltage industrial components > Coil for low-voltage

Eaton Frequency Converters

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $148.35
Unit price: $148.35

Quantity Price
1+$148.35
2+$131.25
3+$124.28
4+$122.61
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Often bought together

More info



Main choke, three-phase, 550 V + 0% (50/60 Hz), V AC, 16 A, 1.84 mH
Main choke, rated operating voltage 480 V AC, three-phase, uk =4%

General specifications
Product name
Eaton DX Mains choke
Part no.
DX-LN3-016
EAN
4015082695033
Product Length/Depth
71 millimetre
Product height
138 millimetre
Product width
140 millimetre
Product weight
2.9 kilogram
Compliances
CE Marked
Certifications
UL 508C
UL Listed
CSA Std. C22.2 No. 14
CE
VDE 0570 Part 2-20/2001-04
CSA-C22.2 No. 14
IEC/EN61800-5
IEC/EN 61558-2-20-2000
UL
UL report applies to both US and Canada
UL Category Control No.: XPTQ2, XPTQ8
Certified by UL for use in Canada
IEC/EN61800-3
CSA
UL File No.: E167225
CSA
UL
Product Tradename
DX
Product Type
Accessory
Product Sub Type
Mains choke
Features & Functions
Fitted with:
Terminations
PE stud
Number of phases
3
Number of poles
Three-pole
General information
Degree of protection
IP20
NEMA Other
Duty factor
100 %
Insulation class
B
Product Category
Accessories
Suitable as
Net reactance coil
Suitable for
Branch circuits, (UL/CSA)
Switching frequency
0 kHz
Used with
DL1
DA1
DC1
SVX
DE1
SPX
DA1, DB1, DC1, DE1, DE11, DM1, SPX, SVX
Ambient conditions, mechanical
Mounting position
Standing vertically
Suspended horizontally
Free surrounding areas > 50 mm
Shock resistance
3 shocks
Shock duration: 11 ms
Vibration resistance
10 - 55 Hz, 0.35 mm
0 - 150 Hz, 1 g
Climatic environmental conditions
Altitude
Max. 5000 m with current reduction
Max. 1000 m
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - max
85 °C
Ambient storage temperature - min
-25 °C
Operating temperature details
-25 - 40 °C (up to 70 °C with current derating)
Terminal capacities
Terminal capacity
4 mm²
20 - 10 AWG
Tightening torque
0.8 Nm, Screw terminals
Electrical rating
Permissible connection voltage
Max. 550 V AC (50/60 Hz)
Rated current (Ith) at rated voltage DC - max
16 A
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Rated inductance
1.84 mH
Rated operational current (Ie) - min
16 A
Rated operational current (Ie) - max
16 A
Rated operational voltage (Ue) - max
550 V
Relative short-circuit voltage
4 %
Voltage rating - max
480 V
Voltage sag Uk
4 %
Design verification
Heat dissipation capacity Pdiss
0 W
Rated operational current for specified heat dissipation (In)
16 A
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Coil for low-voltage (EC002563)
Electric engineering, automation, process control engineering / Electronic coil and filter / Electronic choke coil / Electronic choke coil (unspecified) (ecl@ss13-27-42-01-90 [ADJ199012])
Suitable as interference suppression reactance coil
No
Suitable as net reactance coil
Yes
Suitable as commutation reactance coil
No
Suitable as ripple filter choke
No
Suitable as output reactance coil
No
Number of poles, primary side
3
Rated clock frequency
0 kHz
Rated operating frequency
50 - 60 Hz
Max. rated operation voltage Ue
550 V
Rated current AC
16 - 16 A
Max. rated current (Ith) at rated voltage DC
16 A
Rated inductance
1.84 mH
Degree of protection (IP)
IP20
Relative short circuit voltage
4 %
Resonance frequency
0 Hz
Degree of protection (NEMA)
Other

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.