Product name
Eaton xEnergy Safety Ci empty enclosure insulated
Product Length/Depth
150 millimetre
Product height
375 millimetre
Product width
375 millimetre
Product weight
2.523 kilogram
Certifications
EN 61439-2
EN 62208
Product Tradename
xEnergy Safety Ci
Product Type
Empty enclosure
Product Sub Type
Insulated
Type
Basic enclosurePanel enclosuresxEnergy Safety Ci
Technical Data - Electrical
Technical Data - Mechanical
Surface finishing
Resistant to corrosion
Surface treatment
Resistant to corrosion
Enclosure material
Plastic
Width in number of modular spacings
15
Mounting depth with mounting plate
125 mm
Mounting method
Surface mounted (plaster)
Material
Glass-fibre reinforced polycarbonate (base)
Halogen free
Non-reinforced polycarbonate (cover)
Degree of protection
IP65
IK10
Other
Number of conduit inlets
100
Number of openings (flange plates)
4
Cover/door color
Transparent
Cover/door type
Optional
None
Transparent
Plate thickness (cabinet)
6 mm
Plate thickness (cover/door)
6 mm
Saline spray resistance
IEC 60068-2-11
Temperature-rise verification as per IEC 60890
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
21 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
42 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
23 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
22 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
47 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
45 W
Design verification as per IEC/EN 61439 - technical data
Temperature resistance
Temperature resistant: 80 °C (gasket)
Temperature resistant: -40 °C - 120 °C (enclosure)
Temperature resistant: 85 °C (enclosure bolt)
Ambient operating temperature details
-40 °C - 80 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Lower part: 960 °C / cover: 850 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
20 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Features
UV resistance beneath protective shield
Cover with overpressure release
Flammability characteristics (UL)
V2 (cover) (UL94)
V1 (base) (UL94)
Functions
Extension possible
Special features
Housing prepared for distribution boardTwo sides closed, can be folded outtwo sides openSealable cover fastenersIntegrated pressure-relief mechanism for short-circuits
Suitable for
Outdoor use
Lightning protection