EASY410-DC-RE 114293 EATON MOELLER I/O expansion, 24 V DC, 6DI, 4DO relays, easyLink View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

EASY410-DC-RE 114293 EATON MOELLER I/O expansion, 24 V DC, 6DI, 4DO relays, easyLink

EASY410-DC-RE

114293

EATON - MOELLER

Available

Ship on today

I/O expansion, 24 V DC, 6DI, 4DO relays, easyLink

More details


Programmable Relays

easy700/800 - I/O expansions - EATON - MOELLER

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON - MOELLER

Quantity Price
1+$109.35
3+$102.67
6+$99.63
8+$98.57
11+$97.79
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Delivery programme
Product range
  Control relays easyRelay
Multi-function-display MFD-Titan
Product range
  Compact PLCs
Subrange
  I/O expansions digital
Basic function
  Expansions
Description
  Can be used through easyLink
Function
  Expansions EASY…
Accessories
  I/O expansions, digital
Inputs
   
Inputs expansion (number)
  digital: 6
Outputs
   
Type
  Relay
Supply voltage
  24 V DC
Technical data
General
Dimensions (W x H x D)
 mm71.5 x 90 x 58 (4 PE)
Weight
 kg0.2
Climatic environmental conditions
Operating ambient temperature
 °C-25 to + 55
cold as per IEC 60068-2-1
heat as per IEC 60068-2-2
Condensation
  Take appropriate measures to prevent condensation
Storage
ϑ°C-40 - +70
relative humidity
 %5 - 95
Air pressure (operation)
 hPa795 - 1080
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
  IP20
Vibrations (IEC/EN 60068-2-6)
 Hz 
Constant amplitude 0.15 mm
 Hz10 - 57
Constant acceleration 2 g
 Hz57 - 150
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
 Impacts18
Drop to IEC/EN 60068-2-31
Drop heightmm50
Free fall, packaged (IEC/EN 60068-2-32)
 m1
Mounting position
  Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
  II/2
Electrostatic discharge (ESD)
   
applied standard
  IEC EN 61000-4-2, Level 3
Air discharge
 kV8
Contact discharge
 kV6
Burst
 kVaccording to IEC/EN 61000-4-4
Supply cables: 2
Signal cables: 2
power pulses (Surge)
  2 kV (supply cables, symmetrical, EASY...AC)
0.5 kV (supply cables, symmetrical, easy-DC)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
 V10
Insulation resistance
Insulation resistance
  EN 50178
Power supply
Rated operational voltage
UeV24 DC (-15/+20%)
Permissible range
Ue 20.4 - 28.8 V DC
Residual ripple
 %>
CAD data
>Product-specific CAD data
>3D Preview

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Últimas Opiniones de Nuestros Clientes

Todas las valoraciones que recibimos de los artículos que ofrecemos son reales y están verificadas. Un pequeño gesto, pero de mucho valor. Por eso, te agradecemos ese minuto que inviertes en dejarnos tu opinión y calificación sobre los productos, porque nos ayuda a seguir mejorando y a ofrecerte un servicio de todavía mayor calidad.