Product name
Eaton xEnergy Basic empty enclosure
Product Length/Depth
350 millimetre
Product height
1790 millimetre
Product width
1230 millimetre
Product weight
60.1 kilogram
Product Tradename
xEnergy Basic
Product Type
Empty enclosure
Application
Moisture-proof (installation site)
Color
Gray
Light gray (RAL 7035)
Technical Data - Mechanical
Surface finishing
Powder coating
With powder coating
Mounting method
Floor standing distribution board
Detached
Degree of protection
IP55
IK10
Other
Number of connector holes
0
Permissible load of the door(s) according to IEC 62208 - max
0 N
Permissible load of the enclosure according to IEC 62208 - max
0 N
Permissible load of the mounting plate according to IEC 62208 - max
0 N
Cover/door type
Rotary lever
Grade material
Sheet steel
Installation type
Floor installation possible
Temperature-rise verification as per IEC 60890
Heat diss. ambient 35°C delta T: 20°C free stand middle encl. top (IEC 60890)
263 W
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
237 W
Heat diss. ambient 35°C delta T: 35°C free stand middle encl. top (IEC 60890)
528 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
474 W
Heat diss. ambient 35°C delta T:20°C free stand individ. encl. top (IEC 60890)
276 W
Heat diss. ambient 35°C delta T:20°C free stand starting encl. top (IEC 60890)
272 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
244 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
239 W
Heat diss. ambient 35°C delta T:35°C free stand individ. encl. top (IEC 60890)
553 W
Heat diss. ambient 35°C delta T:35°C free stand starting encl. top (IEC 60890)
545 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
489 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
480 W
Thermal dissipation (Delta T = 20 K) according to IEC/TR 60890
0 W
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP55
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
< 0.1 Ω; meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 440 V AC
10.9.3 Impulse withstand voltage
4 kV
10.9.4 Testing of enclosures made of insulating material
Does not apply to metal enclosures.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Suitable for
Metrical mounting