BP-F-400/20/3-F-IVS-W 111404 EATON ELECTRIC Floor standing distribution board View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

BP-F-400/20/3-F-IVS-W 111404 EATON ELECTRIC Floor standing distribution board

BP-F-400/20/3-F-IVS-W

111404

EATON-MOELLER

Floor standing distribution board

More details


Home > EATON - MOELLER

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Delivery programme
Product range
Service distribution board IVS
Basic function
Floor-standing enclosures
Single unit/Complete unit
Complete housing
Degree of Protection
IP30 (only with door)
Description
Profi Plus basic enclosures without door
Exchangeable door hinges
Material
Sheet steel
Surface finish
Polyester powder coating
Phosphated
RAL 9016, traffic white
Colour
RAL 9016, traffic white
Information about equipment supplied
Including mounting system for the IVS mounting units
including insulating surround and mounted insulated support bracket
including cable entry top and bottom, with push-through flange
Width
mm 400
Height
mm 2060
Depth
mm 300
Technical data
General
Standards
EN 60439-1/3
IEC 62208
Protection class
1
Degree of Protection
IP30 (only with door)
Power loss
Max. admissible heat dissipation, ambient air temperature +35 °C
W 202
Weight
kg 31.3
Material characteristics
Material
Sheet steel
Surface treatment
Painting, phosphated and polyester powder coating
Surface finish
Polyester powder coating
Phosphated
RAL 9016, traffic white
Colour
RAL 9016, traffic white
Material characteristics
Type Door
Doors with covered hinges
Can be removed from 90°
door opening angle
167° (single mounting)
60° (combination mounting)
Door interlock
Hinge handle with three-point turn-lock
Cylinder lock
Material properties
Mechanical
Impact resistance
IK07
Cable entry
Various covers allow cable entry from above and/or below
Electrical
Rated operational voltage
Ue V 690
Rated frequency
f Hz 50
Rated operational current
Ie CSA 630
Max. admissible heat dissipation, ambient air temperature +35 °C
W 202
Earthings
M6 weld stud (base frame)
M5 self-tapping screw (enclosure side plate, top/bottom panel)
M6 weld stud (door)
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees, calculated as per IEC 60890
Individual enclosure, free-standing
PV CO 113
Starting enclosure, free-standing
PV CO 103
Middle enclosure, free-standing
PV CO 95
Individual enclosure for wall mounting
PV CO 101
Starting enclosure for wall mounting
PV CO 87
Middle enclosure for wall mounting
PV CO 74
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees, calculated as per IEC 60890
Individual enclosure, free-standing
PV CO 226
Starting enclosure, free-standing
PV CO 206
Middle enclosure, free-standing
PV CO 190
Individual enclosure for wall mounting
PV CO 202
Starting enclosure for wall mounting
PV CO 175
Middle enclosure for wall mounting
PV CO 148
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK07
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
IP30
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
< 0.1 Ω; meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Ui= 440 V AC
10.9.3 Impulse withstand voltage
4 kV
10.9.4 Testing of enclosures made of insulating material
Does not apply to metal enclosures.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.

Datasheet - PDF

Title: Size: Type:
PDF CATALOGUE EATON EN.pdf 51 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.