Standards
EN 61000-6-2
EN 61000-6-4
EN 61131-2
Potential isolation
Yes, through optocoupler
Ambient temperatureAmbient temperature, operation
0 - +55 °C
Ambient temperatureStorage, transport [ϑ]
-25 - +85 °C
Relative humidityRelative humidity
5 - 95 % (indoor), Level RH-2, no condensation (for storage at 45°C)
Ambient conditions, mechanicalDegree of Protection
IP20
Ambient conditions, mechanicalHarmful gases
SO2: 10 (rel. humidity < 75%, no condensation)
H2S: 1.0 (rel. humidity < 75 %,no condensation) ppm
Vibration resistance, operating conditions
according to IEC/EN 60068-2-6
Mechanical shock resistance
according to IEC 60068-2-27 g
Continuous shock resistance (IEC/EN 60068-2-29)
According to IEC 60068-2-29
Drop and topple
According to IEC 60068-2-31, free fall according to IEC 60068-2-32
Electromagnetic compatibility (EMC)ESD [Air/contact discharge]
EN 61000-4-2 kV
Electromagnetic compatibility (EMC)Electromagnetic fields [(0.08…1) / (1,4…2) / (2…2,7) GHz ]
EN 61100-4-2 V/m
Electromagnetic compatibility (EMC)Burst
EN 61100-4-4
Electromagnetic compatibility (EMC)Surge
EN 61100-4-5
Electromagnetic compatibility (EMC)Radiated RFI
EN 61100-4-6 V
Electromagnetic compatibility (EMC)Emitted interference (radiated, high frequency) [(30...230 MHz) / (230...1000 MHz)]
EN 55016-2-3 dB
Electromagnetic compatibility (EMC)Voltage fluctuations/voltage dips
EN 61131-2
Electromagnetic compatibility (EMC)Type test
to EN 61131-2
Other technical data (sheet catalogue)
Rated voltage through supply terminal [UL]
120/230 V AC (45 - 65 Hz)
Rated current consumption from module bus [IMB]
≦ 35 mA
Connectable sensors
Resistive loads
Inductive loads
Lamp loads
Rated voltage through supply terminal [UL]
120/230 V AC (45 - 65 Hz)
Rated current consumption from module bus [IMB]
≦ 35 mA
Rated voltage through supply terminal [UL]
120/230 V AC (45 - 65 Hz)
Rated current consumption from module bus [IMB]
≦ 35 mA
Power loss [P]
Normally 1 W
Output voltageHigh level [UH⁄UA]
> UL- 2 V DC (zero-point switching triac)
Output currentHigh level (rated value) [IH]
0.5 A
Output currentHigh level (permissible range) [IH]
0.02 - 0.5 A
Output currentLow signal [IA]
< 1.5 mA
Surge current [IS]
8 (1 period at 60 Hz) A
Delay on signal change and resistive loadfrom Low to High level
T/2 +1 ms µs
Delay on signal change and resistive loadFrom High to Low signal
T/2 +1 ms µs
Load resistance range
at 120 V AC 240 Ω - 6 kΩ at 230 V AC 460 Ω - 11.5 kΩ
Utilization factor [%]
100 (observe derating) g
Can be connected
Resistive loads
Inductive loads
Lamp loads
Base moduleswith C connection
2-wire/3-wire
XN-S3x-SBC
4-wire
XN-S4x-SBCS
Rated voltage through supply terminal [UL]
120/230 V AC (45 - 65 Hz)
Rated current consumption from module bus [IMB]
≦ 35 mA
Input voltageHigh level [UeH]
> UL(-2 V) V
Base moduleswith C connection
2-wire/3-wire
XN-S3x-SBC
4-wire
XN-S4x-SBCS
Rated voltage through supply terminal [UL]
120/230 V AC (45 - 65 Hz)
Rated current consumption from module bus [IMB]
≦ 35 mA
Power loss [P]
Normally 1 W
Can be connected
Resistive loads
Inductive loads
Lamp loads
Utilization factor [g]
100 %
Base moduleswith C connection
2-wire/3-wire
XN-S3x-SBC
4-wire
XN-S4x-SBCS
Rated voltage through supply terminal [UL]
120/230 V AC (45 - 65 Hz)
Rated current consumption from module bus [IMB]
≦ 35 mA
Rated voltage through supply terminal [UL]
120/230 V AC (45 - 65 Hz)
Rated current consumption from module bus [IMB]
≦ 35 mA
Input voltageHigh level [UeH]
> UL(-2 V) V
Output currentHigh level (permissible range) [IH]
0.02 - 0.5 A
Output currentHigh level (rated value) [IH]
0.5 A
Rated voltage through supply terminal [UL]
120/230 V AC (45 - 65 Hz)
Rated current consumption from module bus [IMB]
≦ 35 mA
Power loss [P]
Normally 1 W
The supply terminal (UL) provides power for the module electronics and for the consumers at the outputs. The total current required for each module consists of the sum of all partial currents.
Part of the XI/ON module’s electronics is supplied with module bus voltage (5 V DC), the other part through the supply terminal (UL).
To increase the maximum output current to up to 1 A, two outputs can be connected in parallel.
Note for table header
The rated current from supply terminal data apply at zero load current.
Applies for resistive load: RLO < 1kΩ