DC1-34030NB-A20N 180464 EATON ELECTRIC Frequency converter 3/3 400 V 30 A 15 kW Transistor Braking View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

DC1-34030NB-A20N 180464 EATON ELECTRIC Frequency converter 3/3 400 V 30 A 15 kW Transistor Braking

DC1-34030NB-A20N

180464

EATON-MOELLER

Frequency converter; 3/3; 400 V; 30 A; 15 kW; Transistor Braking

More details


Power XL Frequency Converters

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Variable frequency drive, 400 V AC, 3-phase, 30 A, 15 kW, IP20/NEMA 0, Brake chopper, FS4
Alternate Catalog No.
DC1-34030NB-A20N
Variable frequency drive, Part group reference (e.g. DIL): DC1, Rated operational voltage: Ue = 400 V AC, 3-phase, 480 V AC, 3-phase, Output voltage with Ve: U2 = 400 V AC, 3-phase, 480 V AC, 3-phase, Mains voltage (50/60Hz): ULN = 380 (-10%) - 480 (+10%) V, Rated operational current At 150% overload: Ie = 30 A, Note: Rated operational current at an operating frequency of 16 kHz and an ambient air temperature of +50 °C, Note: Overload cycle for 60 s every 600 s, Assigned motor rating Note: for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1 at 50 Hz or 1800 min-1 at 60 Hz, Overload cycle for 60 s every 600 s, at 400 V, 50 Hz, Assigned motor rating 150 % Overload: P = 15 kW, 150 % Overload: IM = 30 A, Assigned motor rating Note: at 440 - 480 V, 60 Hz, Assigned motor rating 150 % Overload: P = 20 HP, Assigned motor rating 150 % Overload: IM = 30 A, Degree of Protection: IP20/NEMA 0, Interface/field bus (built-in): OP-Bus (RS485)/Modbus RTU, CANopen®, Fieldbus connection (optional): SmartWire-DT, Fitted with: Brake chopper, 7-digital display assembly, Frame size: FS4, Standards: Specification for general requirements: IEC/EN 61800-2, EMC requirements: IEC/EN 61800-3, Safety requirements: IEC/EN 61800-5-1
[

Delivery program

This item will continue to be available for a limited time only and is being replaced by the following item: 185783, DC1-34030NB-A20CE1
Product range
Variable frequency drives
Part group reference (e.g. DIL)
DC1
Rated operational voltage [Ue]
400 V AC, 3-phase
480 V AC, 3-phase
Output voltage with Ve[U2]
400 V AC, 3-phase
480 V AC, 3-phase
Mains voltage (50/60Hz) [ULN]
380 (-10%) - 480 (+10%) V
Rated operational current [Ie]
At 150% overload [Ie]
30 A
Note
Rated operational current at an operating frequency of 16 kHz and an ambient air temperature of +50 °C
Assigned motor rating
Note
for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1at 50 Hz or 1800 min-1at 60 Hz
Note
Overload cycle for 60 s every 600 s
Note
at 400 V, 50 Hz
150 % Overload [P]
15 kW
150 % Overload [IM]
30 A
Note
at 440 - 480 V, 60 Hz
150 % Overload [P]
20 HP
150 % Overload [IM]
30 A
Degree of Protection
IP20/NEMA 0
Interface/field bus (built-in)
OP-Bus (RS485)/Modbus RTU, CANopen®
Fieldbus connection (optional)
SmartWire-DT
Fitted with
Brake chopper
7-digital display assembly
Frame size
FS4
Connection to SmartWire-DT
yes
in conjunction with DX-NET-SWD3 SmartWire DT module
,

Technical data

General
Standards
Specification for general requirements: IEC/EN 61800-2
EMC requirements: IEC/EN 61800-3
Safety requirements: IEC/EN 61800-5-1
Certifications
CE, UL, cUL, RCM, UkrSEPRO, EAC
Production quality
RoHS, ISO 9001
Climatic proofing [ρw]
< 95%, average relative humidity (RH), non-condensing, non-corrosive %
Ambient temperatureoperation (150 % overload) [ϑ]
-10 - +50 °C
Ambient temperatureStorage [ϑ]
-40 - +60 °C
Mounting position
Vertical
Altitude
0 - 1000 m above sea level
Above 1000 m: 1% derating for every 100 m
max. 4000 m m
Degree of Protection
IP20/NEMA 0
Protection against direct contact
BGV A3 (VBG4, finger- and back-of-hand proof)
Main circuit
SupplyRated operational voltage [Ue]
400 V AC, 3-phase
480 V AC, 3-phase
SupplyMains voltage (50/60Hz) [ULN]
380 (-10%) - 480 (+10%) V
SupplyInput current (150% overload) [ILN]
34.2 A
SupplySystem configuration
AC supply systems with earthed center point
SupplySupply frequency [fLN]
50/60 Hz
SupplyFrequency range [fLN]
48 - 62 Hz
SupplyMains switch-on frequency
Maximum of one time every 30 seconds
Power sectionFunction
Variable frequency drive with internal DC link and IGBT inverter
Power sectionOverload current (150% overload) [IL]
45 A
Power sectionmax. starting current (High Overload) [IH]
175 %
Power sectionNote about max. starting current
for 2 seconds every 20 seconds
Power sectionOutput voltage with Ve[U2]
400 V AC, 3-phase
480 V AC, 3-phase
Power sectionOutput Frequency [f2]
0 - 50/60 (max. 500) Hz
Power sectionSwitching frequency [fPWM]
8
adjustable 4 - 24 (audible) kHz
Power sectionOperation Mode
U/f control
Speed control with slip compensation
Power sectionFrequency resolution (setpoint value) [Δf]
0.1 Hz
Power sectionRated operational currentAt 150% overload [Ie]
30 A
Power sectionNote
Rated operational current at an operating frequency of 16 kHz and an ambient air temperature of +50 °C
Power sectionFitted with
Brake chopper
7-digital display assembly
Power sectionFrame size
FS4
Motor feederNote
for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1at 50 Hz or 1800 min-1at 60 Hz
Motor feederNote
Overload cycle for 60 s every 600 s
Motor feederNote
at 400 V, 50 Hz
Motor feeder150 % Overload [P]
15 kW
Motor feederNote
at 440 - 480 V, 60 Hz
Motor feeder150 % Overload [P]
20 HP
Motor feedermaximum permissible cable length [I]
screened: 100
screened, with motor choke: 200
unscreened: 150
unscreened, with motor choke: 300 m
Motor feederApparent powerApparent power at rated operation 400 V [S]
12 kVA
Motor feederApparent powerApparent power at rated operation 480 V [S]
14.4 kVA
Motor feederBraking functionDC braking torque
max. 100% of rated operational current Ie,variable
Motor feederBraking functionminimum external braking resistance [Rmin]
30 Ω
Motor feederBraking functionSwitch-on threshold for the braking transistor [UDC]
780 V DC V
Control section
Reference voltage [Us]
10 V DC (max. 10 mA) V
Analog inputs
2, parameterizable, 0 - 10 V DC, 0/4 - 20 mA
Analog outputs
1, parameterizable, 0 - 10 V
Digital inputs
4, parameterizable, max. 30 V DC
Digital outputs
1, parameterizable, 24 V DC
Relay outputs
1, parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1)
Interface/field bus (built-in)
OP-Bus (RS485)/Modbus RTU, CANopen®
Assigned switching and protective elements
Power WiringSafety device (fuse or miniature circuit-breaker)IEC (Type B, gG), 150 %
FAZ-B40/3
Power WiringMains contactor150 % overload (CT/IH, at 50 °C)
DILM17
Power WiringMain choke150 % overload (CT/IH, at 50 °C)
DX-LN3-040
Power WiringRadio interference suppression filter (external, 150 %)
DX-EMC34-042
Power WiringRadio interference suppression filter, low leakage currents (external, 150 %)
DX-EMC34-042-L
Power WiringNote regarding radio interference suppression filter
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
DC link connectionBraking resistance10 % duty factor (DF)
DX-BR022-5K1
DC link connectionBraking resistance20 % duty factor (DF)
DX-BR022-9K2
Motor feedermotor choke150 % overload (CT/IH, at 50 °C)
DX-LM3-035
Motor feederSine filter150 % overload (CT/IH, at 50 °C)
DX-SIN3-032
,

Design verification as per IEC/EN 61439

Technical data for design verification
Operating ambient temperature min.
-10 °C
Operating ambient temperature max.
+50 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
,

Approvals

Product Standards
UL 508C; CSA-C22.2 No. 14; IEC/EN61800-3; IEC/EN61800-5; CE marking
UL File No.
E172143
UL Category Control No.
NMMS, NMMS7
CSA File No.
UL report applies to both US and Canada
North America Certification
UL listed, certified by UL for use in Canada
Specially designed for North America
No
Suitable for
Branch circuits
Max. Voltage Rating
3~ 240 V AC IEC: TN-S UL/CSA: "Y" (Solidly Grounded Wey)
Degree of Protection
IEC: IP20
,

Dimensions

]

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.