Standards
Specification for general requirements: IEC/EN 61800-2
EMC requirements: IEC/EN 61800-3
Safety requirements: IEC/EN 61800-5-1
Certifications
CE, UL, cUL, RCM, UkrSEPRO, EAC
Production quality
RoHS, ISO 9001
Climatic proofing [ρw]
< 95%, average relative humidity (RH), non-condensing, non-corrosive %
Ambient temperatureoperation (150 % overload) [ϑ]
-10 - +40 °C
Ambient temperatureStorage [ϑ]
-40 - +60 °C
Mounting position
Vertical
Altitude
0 - 1000 m above sea level
Above 1000 m: 1% derating for every 100 m
max. 4000 m m
Degree of Protection
IP66/NEMA 4X
Protection against direct contact
BGV A3 (VBG4, finger- and back-of-hand proof)
SupplyRated operational voltage [Ue]
115 V AC, single-phase
SupplyNotes
The mains voltage of 115 V is raised to 230 V (output voltage) through an internal voltage double connection.
SupplyMains voltage (50/60Hz) [ULN]
110 (-10%) - 115 (+10%) V
SupplyInput current (150% overload) [ILN]
15.8 A
SupplySystem configuration
AC supply systems with earthed center point
SupplySupply frequency [fLN]
50/60 Hz
SupplyFrequency range [fLN]
48 - 62 Hz
SupplyMains switch-on frequency
Maximum of one time every 30 seconds
Power sectionFunction
Variable frequency drive with internal DC link and IGBT inverter
Power sectionOverload current (150% overload) [IL]
6.45 A
Power sectionmax. starting current (High Overload) [IH]
175 %
Power sectionNote about max. starting current
for 2 seconds every 20 seconds
Power sectionOutput voltage with Ve[U2]
230 V AC, 3-phase
Power sectionOutput Frequency [f2]
0 - 50/60 (max. 500) Hz
Power sectionSwitching frequency [fPWM]
16
adjustable 4 - 32 (audible) kHz
Power sectionOperation Mode
U/f control
Speed control with slip compensation
Power sectionFrequency resolution (setpoint value) [Δf]
0.1 Hz
Power sectionRated operational currentAt 150% overload [Ie]
4.3 A
Power sectionNote
Rated operational current at a switching frequency of 16 kHz and an ambient air temperature of +40 °C
Power sectionPower lossHeat dissipation at rated operational current Ie=150 % [PV]
37.5 W
Power sectionEfficiency [η]
95 %
Power sectionMaximum leakage current to ground (PE) without motor [IPE]
< 1 mA
Power sectionFitted with
7-digital display assembly
Local controls
Power sectionFrame size
FS1
Motor feederNote
for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1at 50 Hz or 1800 min-1at 60 Hz
Motor feederNote
Overload cycle for 60 s every 600 s
Motor feederNote
at 230 V, 50 Hz
Motor feeder150 % Overload [P]
0.75 kW
Motor feederNote
at 220 - 240 V, 60 Hz
Motor feeder150 % Overload [P]
1 HP
Motor feedermaximum permissible cable length [I]
screened: 50
screened, with motor choke: 100
unscreened: 75
unscreened, with motor choke: 150 m
Motor feederBraking functionStandard braking torque
max. 30 % MN
Motor feederBraking functionDC braking torque
max. 100% of rated operational current Ie,variable
Reference voltage [Us]
10 V DC (max. 10 mA) V
Analog inputs
2, parameterizable, 0 - 10 V DC, 0/4 - 20 mA
Analog outputs
1, parameterizable, 0 - 10 V
Digital inputs
4, parameterizable, max. 30 V DC
Digital outputs
1, parameterizable, 24 V DC
Relay outputs
1, parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1)
Interface/field bus (built-in)
OP-Bus (RS485)/Modbus RTU, CANopen®
Assigned switching and protective elements
Power WiringSafety device (fuse or miniature circuit-breaker)IEC (Type B, gG), 150 %
FAZ-B25/1N
Power WiringSafety device (fuse or miniature circuit-breaker)UL (Class CC or J)
25 A
Power WiringMains contactor150 % overload (CT/IH, at 50 °C)
DILEM-… + P1DILEM
Power WiringMain choke150 % overload (CT/IH, at 50 °C)
DX-LN1-018
Power WiringNote regarding radio interference suppression filter
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
Motor feedermotor choke150 % overload (CT/IH, at 50 °C)
DX-LM3-005
Motor feederSine filter150 % overload (CT/IH, at 50 °C)
DX-SIN3-010