EC4P-221-MRAX1 106398 0004519735 EATON ELECTRIC Compact PLC, 24 V DC, 12DI(of 4AI), 6DO(R), 1AO, CAN View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

EC4P-221-MRAX1 106398 0004519735 EATON ELECTRIC Compact PLC, 24 V DC, 12DI(of 4AI), 6DO(R), 1AO, CAN

EC4P-221-MRAX1

106398

0004519735

EATON-MOELLER

Compact PLC, 24 V DC, 12DI(of 4AI), 6DO(R), 1AO, CAN

EC4P-221-MRAX1

More details


PLC's > PLC device set

EC4P PLCs

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



EL-Nummer (Norway)
4519735
Compact PLC, 24 V DC, 12DI(of 4AI), 6DO(R), 1AO, CAN
Compact controller for small and medium-sized automation tasks, programming according to IEC 61131 (CoDeSys), the Ethernet interface and the serial interface (ec4p-222 types) are for the purpose of programming, the communication via UDP and Modbus as well as connection of OPC clients

Delivery program

Expandable: Inputs/outputs and bus systems
individual laser inscription possible with EC4-COMBINATION-*
Description
easyNet/CANopen® on board
Inputs
Digital
12
of which can be used as analog
4
Outputs
Relay 10 A (UL)
6
Analog
1
Supply voltage
24 V DC

Technical data

General
Dimensions (W x H x D)
107.5 x 90 x 72 without/79 with adapter for MCC (6 SU) mm
Weight
0.3 kg
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using 3 fixing brackets ZB4-101-GF1 (accessories)
Terminal capacities
Solid
0.2/4 (AWG 22 - 12) mm2
Flexible with ferrule
0.2/2.5 (AWG 22 - 12) mm2
Standard screwdriver
0.8 x 3.5 mm
Max. tightening torque
0.6 Nm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
LCD display (clearly legible)
0 - 55 °C
Storage [ϑ]
-40 - +70 °C
Relative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95 %
Air pressure (operation)
1080 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations (IEC/EN 60068-2-6)Constant amplitude 0.15 mm
10 - 57 Hz
Vibrations (IEC/EN 60068-2-6)Constant acceleration 2 g
57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
II/2
Electrostatic discharge (ESD)applied standard
IEC/EN 61000-4-2, Level 3
Electrostatic discharge (ESD)Air discharge
8 kV
Electrostatic discharge (ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
10 V/m
Radio interference suppression
EN 55011 Class B, EN 55022 Class B
Burst
IEC/EN 61000-4-4, level 3 kV
BurstSupply cable
2 kV
BurstSignal lines
2 kV
power pulses (Surge)
2 kV (supply cables, symmetrical, EASY...AC)
0.5 kV (supply cables, symmetrical, easy-DC)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Insulation resistance
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
EN 50178
Back-up of real-time clock
Back-up of real-time clock
252U067
① Backup time (hours) with fully charged double layer capacitor
② Service life (years)
Accuracy of the real-time clock
part no. ± 5 (± 0.5 h⁄Year) s/day
Retentive memory
Write cycles of the retentive memory
10000000000 (10¹⁰) (Read-write cycles)
Power supply
Rated operational voltage [Ue]
24 DC (-15/+20%) V
Permissible range [Ue]
20.4 - 28.8 V DC
Residual ripple
≦ 5 %
Input current
normally 140 mA at Ue
Voltage dips
≤ 10
(IEC/EN 61131-2) ms
Heat dissipation [P]
Normally 3.4 W
CPU
Processor
Infineon XC161
MemoryProgram code/data
256/14 segments of 16 KB each kByte
MemoryMarker/retentive data
16/4/4/8 KByte
Cycle time for 1 k of instructions (Bit, Byte)
< 0.3 ms
Interfaces
PRG interface RS232Data transfer rate
4.8, 9.6, 19.2, 38.4, 57.6, 115.2 (character format: 8 bit data, no parity, 1 stop bit) kBit/s
PRG interface RS232Connection types
RJ45-bus
PRG interface RS232Potential isolation
none
PRG interface RS232Master modeData transfer rate
0.3, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 kbit/s
PRG interface RS232Master modeCharacter formats
8E1, 8O1, 8N1, 8N2, 7E2, 7O2, 7N2, 7E1
PRG interface RS232Master modeNumber of transmission bytes in a block
190 bytes
PRG interface RS232Master modeNumber of received bytes in a block
190 bytes
EthernetData transfer rate
10 MBit/s, 100 m Mbit/s
EthernetConnection types
RJ45
EthernetPotential isolation
No
CANopen®Data transfer rate
500 kBit/s, 25 m250 kBit/s, 60m125 kBit/s, 125 m50 kBit/s, 300 m20 kBit/s, 700 m10 kBit/s, 1000 m
CANopen®Bus termination (first and last station)
EASY-NT-R plug (incl. bus terminating resistor 120 Ω)
CANopen®Connection types
2 x RJ45, 8 pole
Master modeNumber
8
Mode slaveStations
max. 126 Number
Mode slavePDO type
Asynchronous, cyclic, acyclic
Mode slaveControl contact rated current
To DS 301 V4
Digital inputs 24 V DC
Number
12
Inputs can be used as analog inputs
4 (I7, I8, I11, I12)
Status Display
LCD-Display
Potential isolation
from the outputs: yes
to network easyNet, easyLink
Rated operational voltage [Ue]
24 V DC
Input voltage
< 5 (I1 - I6, I9 - I10) < 8 (I7, I8, I11, I12) at signal "0"
> 15.0 (I1 - I6, I9, I10) > 8.0 (I7, I8, I11, I12) at signal "1" V DC
Input current on 1 signalInput current at signal 1
3.3 (I1 to I6)
2.2 (I7, I8)
3.3 (I9, I10)
2.2 (I11, I12) mA
Deceleration time
normally 0.02 (I1 - I4), normally 0.25 (I5 - I12) (from ''0'' to "1")
normally 0.02 (I1 - I4), normally 0.25 (I5 - I12) (from ''0'' to "1") ms
Cable length
100 (unshielded) m
Incremental counterNumber of counter inputs
1 (I1, I2, I3, I4)
Incremental counterValue range
32 Bit
Incremental counterCounter frequency
≦ 40 kHz
Incremental counterPulse shape
Square
Incremental counterCounter inputs
I1, I2
Incremental counterReference input
I3
Incremental counterInput for reference switch
I4
Incremental counterCounter inputs I1 and I2, I3 and I4
1
Incremental counterSignal offset
90°
Rapid counter inputsNumber
2 (I1, I2) at 16 Bit or 1 (I1) at 32 Bit
Rapid counter inputsValue range
16/32 Bit
Rapid counter inputsCable length
≦ 20 (screened) m
Rapid counter inputsCounter frequency
≦ 50 kHz
Rapid counter inputsPulse shape
Square
Analog inputs
Number
4 (I7, I8, I11, I12)
Potential isolation
from the outputs: yes
to interface/memory card: no
Input type
DC voltage
Signal range
0-10 V DC
Resolution
0.01 V analog
0.01 V digital
10 Bit (value 0 - 1023)
Input impedance
11.2 kΩ
Accuracy of actual valueWithin a single device
± 2, (I7, I8, I11, I12) ± 0.12 V %
Conversion time, analog/digital
each CPU cycle ms
Input current
< 1 mA
Cable length
≦ 30, screened m
Analog outputs
Number
1
Output type
DC voltage
Signal range
0-10 V DC
Max. output current
0.01 A
Load resistance
1 kΩ
Overload and short-circuit protection
Yes
Resolution
0.01 V DC analog
10 Bit (value 0 - 1023) digital
Recovery time
100 µs
Accuracy-25 °C - 55 °C
2 %
Accuracy25°C
1 %
Conversion time, analog/digital
each CPU cycle ms
Relay outputs
Outputs in groups of
1
Parallel switching of outputs for increased output
Not permissible
Protection of an output relay
Miniature circuit-breaker B16 or fuse 8 A (slow)
Potential isolation
from power supply: yes
From the inputs: yes
in groups
Safe isolation according to EN 50178: 300 V AC
Basic isolation: 600 V AC
Lifespan, mechanical [Operations]
10 x 106
ContactsConventional thermal current (10 A UL)
8 A
ContactsRecommended for load: 12 V AC/DC
> 500 mA
ContactsShort-circuit-proof cos ϕ = 1, characteristic B16 at 600 A
16 A
ContactsShort-circuit-proof cos ϕ = 0.5 to 0.7, characteristic B16 at 900 A
16 A
ContactsRated impulse withstand voltage Uimpof contact coil
6 kV
ContactsRated operational voltage [Ue]
250 V AC
Rated insulation voltage [Ui]
250 V AC
Safe isolation according to EN 50178
300 between coil and contact
300 between two contacts V AC
Making capacityAC–-15, 250 V AC, 3 A (600 ops./h) [Operations]
300000
Making capacityDC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) [Operations]
200000
Breaking capacityAC-15, 250 V AC, 3 A (600 Ops./h) [Operations]
300000
Breaking capacityDC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h) [Operations]
200000
Filament bulb load1000 W at 230/240 V AC [Operations]
25000
Filament bulb load500 W at 115/120 V AC [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 10 x 58 W at 230/240 V ACWith upstream electrical device [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 10 x 58 W at 230/240 V ACUncompensated [Operations]
25000
Fluorescent lamp loadFluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated [Operations]
25000
Switching frequencyMechanical operations
10 x 106
Switching frequencySwitching frequency
10 Hz
Switching frequencyResistive load/lamp load
2 Hz
Switching frequencyInductive load
0.5 Hz
UL/CSAUninterrupted current at 240 V AC
10 A
UL/CSAUninterrupted current at 24 V DC
8 A
UL/CSAACControl Circuit Rating Codes (utilization category)
B 300 Light Pilot Duty
UL/CSAACMax. rated operational voltage
300 V AC
UL/CSAACmax. thermal continuous current cos ϕ = 1 at B 300
5 A
UL/CSAACmax. make/break cos ϕ ≠ capacity 1 at B 300
3600/360 VA
UL/CSADCControl Circuit Rating Codes (utilization category)
R 300 Light Pilot Duty
UL/CSADCMax. rated operational voltage
300 V DC
UL/CSADCMax. thermal uninterrupted current at R 300
1 A
UL/CSADCMax. make/break capacity at R 300
28/28 VA
Network easyNet
Bus termination (first and last station)
EASY-NT-R plug (incl. bus terminating resistor 120 Ω)

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
0 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
3.4 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+55 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

PLC's (EG000024) / PLC device set (EC002581)
Electric engineering, automation, process control engineering / Control / Programmable logic control (SPS) / PLC device set ([email protected] [BAA707013])
Contains function building blocks
Yes
Contains basic device
Yes
Contains module rack
No
Contains power supply
Yes
Contains analogue input module
Yes
Contains analogue output module
Yes
Contains digital input module
Yes
Contains digital output module
Yes
Contains function module
Yes
Contains technology module
No
Contains communication module
Yes
Contains memory unit
Yes
Contains simulation module
No
Contains connection cable
No
Contains control unit
No
Contains monitor
No
Contains programming software
No
Contains engineering software
Yes
Contains visualization
No
Contains libraries
Yes
Contains documentation
Yes
Contains other components
Yes
Software preinstalled
No

Approvals

Product Standards
IEC: see Technical Data; UL508; CSA-C22.2 No. 0-M; CSA-C22.2 No. 142-M; CE marking
UL File No.
E135462
UL Category Control No.
NRAQ
CSA File No.
012528
CSA Class No.
2252-01
North America Certification
UL listed, CSA certified
Specially designed for North America
No
Current Limiting Circuit-Breaker
No
Degree of Protection
IEC: IP20, UL/CSA Type: -

Dimensions

2724DIM-5

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.