PKZM4-16-CB 132591 EATON ELECTRIC Circuit-breaker, 3p, Ir 10-16A, NA type View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PKZM4-16-CB 132591 EATON ELECTRIC Circuit-breaker, 3p, Ir 10-16A, NA type

PKZM4-16-CB

132591

XTPR016DCBNL

EATON-MOELLER

Circuit-breaker, 3p, Ir=10-16A, NA type

PKZM4-16-CB

Circuit-breaker, Ir= 10 - 16 A, Screw terminals, Terminations: IP2X

More details


Low-voltage industrial components > Power circuit-breaker for trafo/generator/installation protection

Circuit Breakers PKZ

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $170.02
Unit price: $170.02

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

More info



Circuit-breaker, Ir= 10 - 16 A, Screw terminals, Terminations: IP2X
Circuit-breakers for the protection of cables and conductors, UL489, CSA22.2 no. 5-09, not usable as a main switch

General specifications
Product name
Eaton Moeller® series PKZM4 Motor-protective circuit-breaker
Part no.
PKZM4-16-CB
EAN
4015081295265
Product Length/Depth
160 millimetre
Product height
165 millimetre
Product width
55 millimetre
Product weight
1.18 kilogram
Compliances
CE Marked
Certifications
UL 489
CE
CSA File No.: 165628
UL
CSA-C22.2 No. 5-09
UL File No.: E31593
VDE 0660
CSA
UL Category Control No.: DIVQ
CSA Class No.: 1432-01
IEC/EN 60947-2
Product Tradename
PKZM4
Product Type
Motor-protective circuit-breaker
Product Sub Type
None
Catalog Notes
Not usable as a main switch
Features & Functions
Actuator type
Turn button
Features
Complete device with protection unit
Functions
Line and cable protection
For protection of cables and conductors
Number of poles
Three-pole
General information
Connection
Screw terminals
Degree of protection
Terminals: IP2X
IP20
Lifespan, electrical
30,000 operations (at 400V, AC-3)
Lifespan, mechanical
30,000 Operations (Main conducting paths)
Operating frequency
40 Operations/h
Overvoltage category
III
Pollution degree
3
Product category
Motor protective circuit breaker
Protection
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)
6000 V AC
Shock resistance
15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Suitable for
DIN rail (top hat rail) mounting
Feeder and branch circuit as BCPD, (UL/CSA)
Temperature compensation
-5 - 40 °C to IEC/EN 60947, VDE 0660
≤ 0.25 %/K, residual error for T > 40°
-25 - 55 °C, Operating range
Climatic environmental conditions
Altitude
Max. 2000 m
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient operating temperature (enclosed) - min
25 °C
Ambient operating temperature (enclosed) - max
40 °C
Ambient storage temperature - min
40 °C
Ambient storage temperature - max
80 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
Terminal capacity (flexible with ferrule)
1 x (0.75 - 16) mm², ferrule to DIN 46228
2 x (0.75 - 16) mm²
Terminal capacity (flexible with ferrule AWG)
14 - 8
Terminal capacity (solid)
2 x (0.75 - 16) mm²
1 x (0.75 - 16) mm²
Terminal capacity (solid/stranded AWG)
14 - 6
Stripping length (main cable)
14 mm
Tightening torque
3.3 Nm, Screw terminals, Main cable
Electrical rating
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Rated operational current (Ie)
16 A
Rated operational voltage (Ue) - min
600 V
Rated operational voltage (Ue) - max
690 V
Rated uninterrupted current (Iu)
16 A
Short-circuit rating
Rated short-circuit breaking capacity Icu at 400 V AC
65 kA
Short-circuit current
60 kA DC, up to 250 V DC, Main conducting paths
Short-circuit current rating (UL 489 CSA 22.2-5.09)
65 kA, 480 Y/277 V, SCCR (UL/CSA)
22 kA, 600 Y/347 V, SCCR (UL/CSA)
Short-circuit release
248 A, Irm, Setting range max.
Basic device fixed 15.5 x Iu, Trip Blocks
± 20% tolerance, Trip blocks
Switching capacity
Switching capacity
16 A, AC-3 up to 690 V
16 A (3 contacts in series), DC-5 up to 250V
Contacts
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Trip blocks
Overload release current setting - min
0 A
Overload release current setting - max
16 A
Design verification
Equipment heat dissipation, current-dependent Pvid
14.1 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
4.7 W
Rated operational current for specified heat dissipation (In)
16 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Power circuit-breaker for trafo/generator/installation protection (EC000228)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Circuit breaker for power transformer, generator and system protection (ecl@ss13-27-37-04-09 [AJZ716018])
Rated permanent current Iu
16 A
Rated voltage
600 - 690 V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65 kA
Overload release current setting
0 - 16 A
Adjustment range short-term delayed short-circuit release
0 - 0 A
Adjustment range undelayed short-circuit release
0 - 224 A
Power loss
14.1 W
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
No
Type of electrical connection of main circuit
Screw connection
Suitable for DIN rail (top hat rail) mounting
Yes
DIN rail (top hat rail) mounting optional
Yes
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
No
With integrated under voltage release
No
Number of poles
3
Position of connection for main current circuit
Other
Type of control element
Turn button
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
No
Degree of protection (IP)
IP20

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.