+NZM3-4-XKCU 266782 EATON ELECTRIC Box terminal, 4p, bottom up to 630A, size 3 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

+NZM3-4-XKCU 266782 EATON ELECTRIC Box terminal, 4p, bottom up to 630A, size 3

+NZM3-4-XKCU

266782

EATON-MOELLER

Box terminal, 4p, bottom up to 630A, size 3. Can only be sold assembled.

+NZM3-4-XKCU

Box terminal, 4p, bottom up to 630A, size 3

More details


Low-voltage industrial components > Wiring set for power circuit breaker

Circuit Breakers NZM Accessories

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article is restricted. Please ask us for a quotation and we will check if there are units available or we will offer you an alternative product.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Box terminal, 4p, bottom up to 630A, size 3
Optional accessories for circuit-breaker series NZM offers a comprehensive portfolio of application possibilities for worldwide use. Modular functional groups make mounting flexible and simple. Notes: part no. suffix and part no. contain parts for a circuit-breaker side at top or bottom for 3 or 4 pole circuit-breakers. Conversion kit for circuit-breaker with screw connection. Fitted within the switch housing. O = fitted at the top. U = fitted at the bottom. U e ≧ 525 VAC. Use NZM3(-4)-XKSA cover. Use ferrules with flexible and highly flexible conductors., observe limited terminal capacity through sleeve . Can be used for: NZM3(-4), PN3(-4), N(N/O)3(-4)

General specifications
Product name
Eaton Moeller series NZM connection type
Part no.
+NZM3-4-XKCU
EAN
4015082667825
Product Length/Depth
80 millimetre
Product height
60 millimetre
Product width
80 millimetre
Product weight
0.53 kilogram
Compliances
IEC
RoHS conform
Product Tradename
NZM
Product Type
Accessories
Product Sub Type
Connection type
Delivery program
Type
AccessoryBox terminalTerminal
Number of poles
Four-pole
Amperage Rating
≦ 630 A
Frame
NZM3
Suitable for
Four-pole
Copper cable
Used with
NZM3(-4), PN3(-4), N(S)3(-4)
Technical Data - Mechanical
Mounting position
Fitted at the bottom
Technical Data - Mechanical - Terminals
Terminal capacity (stranded cable)
35 mm² - 240 mm² (1x)
16 mm² - 120 mm² (2x)
2 - 500 AWG/kcmil (1x)
Terminal capacity (copper strip)
630 A: 10 segments of 24 mm x 1 mm + 5 segments of 24 mm x 1 mm or 8 segments of 24 mm x 1 mm (2x)
Max. 500 A: 6 segments of 16 mm x 0.8 mm - 10 segments of 24 mm x 1 mm or 11 segments of 21 mm x 1 mm
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Additional information
Model
Other

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Wiring set for power circuit breaker (EC002050)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Wiring set for circuit breaker (ecl@ss13-27-37-04-24 [ACN957016])
Suitable for number of poles
4
Model
Other

Datasheet - PDF

Title: Size: Type:
+NZM3-4-XKCU 266782 EN_266782.pdf 110 Kbytes   +NZM3-4-XKCU  266782 EN_266782.pdf

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.