Product name
Eaton XIOC Output module
Product Length/Depth
100 millimetre
Product height
95 millimetre
Product width
30 millimetre
Product weight
0.135 kilogram
Certifications
UL
IEC/EN 61131-2
CSA Class No.: 2252-01
CSA-C22.2 No. 0-M
CSA
UL Category Control No.: NRAQ
CSA File No.: 012528
UL508
CSA-C22.2 No. 142-M
EN 50178
UL File No.: E135462
CE
Product Type
Output module
Electric connection type
Screw-/spring clamp connection
Features
Output, voltage
Input, voltage
Analog outputs configurable
Analog inputs configurable
Admissible range
20.4 – 28.8 V (11.8 – 14.4 V), Power supply
Current consumption
100 mA, external, Outputs
Used with
XC100/200 (expandable with up to 15 XI/OC modules)
Ambient conditions, mechanical
Impact resistance
500 g/⌀ 50 mm ±25 g
Shock resistance
15 g, Mechanical, Shock duration 11 ms
Vibration resistance
10 - 57 Hz, ± 0.075 mm
57 - 150 Hz ± 1.0 mm
Climatic environmental conditions
Ambient operating temperature - min
0 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-25 °C
Ambient storage temperature - max
70 °C
Electro magnetic compatibility
Emitted interference
Class A (according to DIN/EN 55011/22)
Terminals
Optionally, screw terminals or spring-loaded terminals for digital/analog modules
Power supply
24 V DC (-15/+20 %), approx. 150 mA
Rated operational voltage
24 (12) V DC
Supply voltage at DC - max
24 V DC
Connection type
2-core screened cable (≤ 20 m), Outputs
Plug-in terminal block, Outputs
Conversions
≤ 5 ms, Inputs
Number of inputs (analog)
0
Number of outputs (analog)
4
Output
4 Outputs (0 - 10 V)
Outputs
Output voltage
4
0 - 10 V DC
Total error
≤ ±1 % (of the full-scale value), Outputs
Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Circuit within each channel: Opto-isolated
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0.5 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.