UA16-30-10 1SBL181022R8010 ABB UA16-30-10 220-230V 50Hz / 230-240V 60Hz Contactor View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

UA16-30-10 1SBL181022R8010 ABB UA16-30-10 220-230V 50Hz / 230-240V 60Hz Contactor

1SBL181022R8010

ABB

UA16-30-10 220-230V 50Hz / 230-240V 60Hz Contactor

More details


Low-voltage industrial components > Capacitor contactor

Contactors and overload relays > Contactors "A" FRCTLP

* Brand new product in its original packaging covered by the warranties and certifications provided by ABB

Total price: $60.67
Unit price: $60.67

Quantity Price
1+$60.67
2+$53.48
3+$51.95
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



UA16 3-pole contactors for capacitor switching, can be used for the switching of capacitor banks whose inrush current peaks are less than or equal to 100 times nominal rms current. The table below gives the permissible powers according to operational voltage and temperature close to the contactor. It also specifies the maximum peak current Î values accepted by the contactor. The capacitors must be discharged (maximum residual voltage at terminals ≤ 50 V) before being re-energized when the contactors are making. In these conditions, electrical durability of contactors is equal to 100 000 operating cycles. The UA.. series 3-pole contactors are of the block type design. - Main poles and auxiliary contacts: 3 main poles, 1 built-in auxiliary contact - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.

Ordering

  • EAN:
    3471522254801
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85369085

Dimensions

  • Product Net Width:
    44mm
  • Product Net Depth:
    74mm
  • Product Net Height:
    74mm
  • Product Net Weight:
    0.340kg

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    78 mm
  • Package Level 1 Length:
    76 mm
  • Package Level 1 Height:
    47 mm
  • Package Level 1 Gross Weight:
    0.34 kg
  • Package Level 1 EAN:
    3471522254801
  • Package Level 2 Units:
    63 piece
  • Package Level 3 Units:
    1220 piece

Technical

  • Number of Main Contacts NO:
    3
  • Number of Main Contacts NC:
    0
  • Number of Auxiliary Contacts NO:
    1
  • Number of Auxiliary Contacts NC:
    0
  • Rated Operational Voltage:
    Auxiliary Circuit 690 V
    Main Circuit 690 V
  • Rated Frequency (f):
    Supply Circuit 50 Hz
    Supply Circuit 60 Hz
  • Conventional Free-air Thermal Current (Ith):
    acc. to IEC 60947-5-1, q = 40 °C 16 A
  • Rated Operational Current AC-15 (Ie):
    (220 / 240 V) 4 A
    (24 / 127 V) 6 A
    (380 / 440 V) 3 A
    (500 V) 2 A
    (690 V) 2 A
  • Short-Circuit Protective Devices:
    Auxiliary Circuit - gG Type Fuses 10 A
    gG Type Fuses 1.5 ... 1.8 A
  • Rated Short-time Withstand Current (Icw):
    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 140 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 30 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
    for 0.1 s 140 A
    for 1 s 100 A
  • Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A
  • Rated Operational Current DC-13 (Ie):
    (125 V) 1.1 / 138 A
    (24 V) 6 / 144 A
    (250 V) 0.55 / 138 A
    (48 V) 2.8 / 134 A
    (72 V) 2 / 144 A
  • Rated Insulation Voltage (Ui):
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
  • Rated Impulse Withstand Voltage (Uimp):
    8 kV
  • Mechanical Durability:
    10 million
  • Maximum Mechanical Switching Frequency:
    3600 cycles per hour
  • Coil Operating Limits:
    (acc. to IEC 60947-4-1)0.85 ... 1.1 x Uc (at θ ≤ 55 °C) °C
  • Rated Control Circuit Voltage (Uc):
    50 Hz 220 … 230 V
    60 Hz 230 … 240 V
  • Coil Consumption:
    Pull-in at Max. Rated Control Circuit Voltage 50 Hz 70 V·A
    Pull-in at Max. Rated Control Circuit Voltage 60 Hz 80 V·A
    Average Holding Value 50 / 60 Hz 8 V·A
    Average Holding Value 50 / 60 Hz 2 W
    Average Pull-in Value 50 Hz 70 V·A
    Average Pull-in Value 60 Hz 70 V·A
  • Operate Time:
    Between Coil Energization and NO Contact Closing 10 ... 26 ms
    Between Coil De-energization and NO Contact Opening 4 ... 11 ms
  • Connecting Capacity-Main Circuit:
    Flexible with Cable End0.75 ... 2.5 mm²
    Rigid Cable1 ... 4 mm²
  • Connecting Capacity-Auxiliary Circuit:
    Flexible with Cable End0.75 ... 2.5 mm²
    Rigid Cable1 ... 4 mm²
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
  • Connecting terminals (delivered in open position) Main poles:
    M 3.5 (+,-) pozidriv 2 screws with cable clamp
  • Terminal Type:
    Screw Terminals

Environmental

  • Ambient Air Temperature:
    Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C
    Near Contactor for Operation in Free Air (Uc) -40 ... +70 °C
    Close to Contactor for Storage -60 ... +80 °C
  • Climatic Withstand:
    acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
  • Maximum Operating Altitude Permissible:
    3000 m
  • RoHS Status:
    No declaration needed

Certificates and Declarations (Document Number)

Classifications

  • ETIM 5:
    EC001079 - Capacitor magnet contactor
  • UNSPSC:
    39121529

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.