Special features
IP30Protection Class IIPlastic enclosure with sheet steel door, white (RAL 9016)
Type
Basic deviceInstallation distribution boardKLV energy
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
850 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
10.9.3 Impulse withstand voltage
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
Fitted with:
Installation instructions
Neutral and protective conductor terminals with SK screw terminal technology
Device support rails
Spirit level for leveling
Imprintable sheet
3D adjustment element for mounting designed to adjust the mounting depth by up to 18 mm
Hollow-wall anchor
Front cover
Wall trough
Door/Frame
Cable retainer
Used with
Installation distribution board
KLV energy
Basic device
Cable entry postion
Cable entries on top and bottom, side, back plate
Heat diss. ambient 35°C delta T:20°C flush mount individ. encl. top(IEC 60890)
Heat diss. ambient 35°C delta T:35°C flush mount individ. encl. top(IEC 60890)
Width in number of modular spacings
Ambient operating temperature details
Application
Indoor (installation site)
Color
Traffic white (RAL 9016)
White
Frequency rating of contacts
Degree of protection
IK05 (impact resistance)
IP30
Number of module space units per row
Protective shrouding material
Functions
Extension possible
Basic device
Material
Sheet steel, powder-coated
Polystyren (plastic)
Mounting method
DIN-rail
Hollow wall
Hollow-wall mounting
PE and N terminal number and cross section
N: 25 x (0.75 mm² - 16 mm²)
PE: 25 x (0.75 mm² - 16 mm²)
N - Fi: 4x (0.75 mm² - 16 mm²)