DILMP160(RAC24) 109914 EATON MOELLER XTCF160G00T Contactor 4p 160A DILMP160(24vac) Ver más grande
Las imágenes son sólo a título ilustrativo. Por favor, revise la ficha técnica.

DILMP160(RAC24) 109914 EATON MOELLER XTCF160G00T Contactor 4p 160A DILMP160(24vac)

DILMP160(RAC24)

109914

EATON - MOELLER

Disponible

Envío el hoy

Producto bajo demanda, no admite devolución.

XTCF160G00T Contactor 4p 160A DILMP160(24vac)

Más detalles


Contactores Electricos

Contactores DIL - EATON - MOELLER

Contactores tetrapolares DILMP - EATON - MOELLER

* Producto nuevo en su embalaje original con todas las garantías y certificaciones de EATON - MOELLER

CantidadPrecio
1+$225.27
2+$220.63
3+$220.60
*Este precio es por unidad y muestra el valor neto (no incluye impuestos indirectos si son aplicables).

Cómo funciona

¿Cómo funciona ésto?

1 Añada los productos de su elección al carro de la compra
2 Introduzca sus datos de contacto y envíe la solicitud
3 Le enviaremos un email con un presupuesto para esos productos
4 Usted simplemente finalice la compra y recibirá su pedido

Existen varias opciones para realizar el pago
- Tarjeta de crédito
- Transferencia
- PayPal


Productos relacionados

Más Información



Delivery programme
Product range
  Contactors
Application
  Contactors for 4 pole electric consumers
Subrange
  Contactors up to 200 A, 4 pole
Utilization category
  AC-1: Non-inductive or slightly inductive loads, resistance furnaces
NAC-3: Normal AC induction motors: starting, switch off during running
Connection technique
  Screw terminals
Pole
  4 pole
Rated operational current
   
AC-1
   
Conventional free air thermal current, 3 pole, 50 - 60 Hz
   
at 40 °C
Ith =IeA160
at 50 °C
Ith =IeA150
at 60 °C
Ith =IeA138
Contact sequence
  
General
Standards
  IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
   
AC operated
Operationsx 10610
DC operated
Operationsx 10610
Operating frequency, mechanical
   
AC operated
Operations/h 3600
DC operated
Operations/h 3600
Climatic proofing
  Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
   
Open
 °C-25 - +60
Enclosed
 °C- 25 - 40
Storage
 °C- 40 - 80
Mounting position
   
Mounting position
  
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA160
Heat dissipation per pole, current-dependent
PvidW12.1
Equipment heat dissipation, current-dependent
PvidW36.3
Static heat dissipation, non-current-dependent
PvsW2.3
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C60
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Power contactor, AC switching (EC000066)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Power contactor, AC switching ([email protected] [AAB718012])
Rated control supply voltage Us at AC 50HZ
 V24 - 24
Rated control supply voltage Us at AC 60HZ
 V24 - 24
Rated control supply voltage Us at DC
 V0 - 0
Voltage type for actuating
  AC
Rated operation current Ie at AC-1, 400 V
 A160
Rated operation current Ie at AC-3, 400 V
 A95
Rated operation power at AC-3, 400 V
 kW45
Rated operation current Ie at AC-4, 400 V
 A65
Rated operation power Ie at AC-4, 400 V
 kW33
Modular version
  No
Number of auxiliary contacts as normally open contact
  0
Number of auxiliary contacts as normally closed contact
  0
Type of electrical connection of main circuit
  Screw connection
Number of normally closed contacts as main contact
  0
Number of main contacts as normally open contact
  4
Approvals
Product Standards  IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No.  E29096
UL Category Control No.  NLDX
CSA File No.  012528
CSA Class No.  2411-03, 3211-04
North America Certification  UL listed, CSA certified
Specially designed for North America  No
Characteristics
IL03407049Z (AWA2100-2356) 4 pole Contactor
 
>>

Datasheet - PDF

Opiniones: (0)

Ningún comentario por el momento.

Añadir comentario
ocultar
Valoración:
Nombre:
Email:
Título:
Opinión:
  Captcha
  Añadir comentario
¿Tiene dudas con la compra?

Si tiene dudas con la compra, puede visitar los siguientes links o enviarnos un correo

Por favor, espere.





* Campos obligatorios