NHI-E-11-PKZ0 082882 EATON MOELLER XTPAXFA11 Contacto aux. Frontal 1nc+1no Ver más grande
Las imágenes son sólo a título ilustrativo. Por favor, revise la ficha técnica.

NHI-E-11-PKZ0 082882 EATON MOELLER XTPAXFA11 Contacto aux. Frontal 1nc+1no

NHI-E-11-PKZ0

082882

EATON - MOELLER

Disponible

Envío hoy

XTPAXFA11 Contacto aux. Frontal 1nc+1no

Más detalles


Interruptores Protectores Motor Guardamotores

Interruptores protectores de motor PKZ - EATON - MOELLER

Interruptor protector motor PKZ (Accesorios) - EATON - MOELLER

* Producto nuevo en su embalaje original con todas las garantías y certificaciones de EATON - MOELLER

CantidadPrecio
1+$6.26
21+$5.24
41+$5.12
61+$5.05
81+$5.01
*Este precio es por unidad y muestra el valor neto (no incluye impuestos indirectos si son aplicables).

Cómo funciona

¿Cómo funciona ésto?

1 Añada los productos de su elección al carro de la compra
2 Introduzca sus datos de contacto y envíe la solicitud
3 Le enviaremos un email con un presupuesto para esos productos
4 Usted simplemente finalice la compra y recibirá su pedido

Existen varias opciones para realizar el pago
- Tarjeta de crédito
- Transferencia
- PayPal


Productos relacionados

Más Información



Delivery programme
Product range
  Accessories
Accessories
  Standard auxiliary contact
For use with
  PKZ0(4) standard auxiliary contacts
Contacts
   
N/O = Normally open
  1 N/O
N/C = Normally closed
  1 NC
Contact diagram
  
Auxiliary contacts
Rated impulse withstand voltage
UimpV AC4000
Overvoltage category/pollution degree
  III/3
Rated operational voltage
UeV 
 
UeV AC440
 
UeV DC250
Safe isolation to EN 61140
   
Between auxiliary contacts and main contacts
 V AC690
Rated operational current
IeA 
AC-15
   
220 - 240 V
IeA1
DC-13 L/R - 100 ms
   
24 V
IeA2
Lifespan
 S 
Lifespan, mechanical
Operationsx 106> 0.1
Lifespan, electrical
Operationsx 1060.1
Control circuit reliability
Failure rateλ<10-8, < one failure at 100 million operations
(at Ue = 24 V DC, Umin = 17 V, Imin = 5.4 mA)
Short-circuit rating without welding
   
Fuse
 A gG/gL10
Terminal capacities
Solid or flexible conductor, with ferrule
 mm20,75 - 1,5
Solid or stranded
 AWG18 - 16
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA1
Heat dissipation per pole, current-dependent
PvidW0.01
Equipment heat dissipation, current-dependent
PvidW0
Static heat dissipation, non-current-dependent
PvsW0
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C55
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Auxiliary contact block (EC000041)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Auxiliary switch block ([email protected] [AKN342010])
Number of contacts as change-over contact
  0
Number of contacts as normally open contact
  1
Number of contacts as normally closed contact
  1
Rated operation current Ie at AC-15, 230 V
 A1
Type of electric connection
  Screw connection
Model
  Top mounting
Mounting method
  Front fastening
Approvals
Product Standards  UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking
UL File No.  E36332
UL Category Control No.  NLRV
CSA File No.  165628
CSA Class No.  3211-05
North America Certification  UL listed, CSA certified
Specially designed for North America  No
Dimensions
IL03402034Z (AWA1210-1945) Motor-protective circuit-breaker, Starter
 
>
>>

Datasheet - PDF

Opiniones: (0)

Ningún comentario por el momento.

Añadir comentario
ocultar
Valoración:
Nombre:
Email:
Título:
Opinión:
  Captcha
  Añadir comentario
¿Tiene dudas con la compra?

Si tiene dudas con la compra, puede visitar los siguientes links o enviarnos un correo

Por favor, espere.





* Campos obligatorios