Type 1 / Class I / B arrester lightning current arrester with encapsul - PHOENIX CONTACT - FLT 35-260 - 2800110 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

Type 1 / Class I / B arrester lightning current arrester with encapsul - PHOENIX CONTACT - FLT 35-260 - 2800110

FLT 35-260





Ship on today

Type 1 / Class I / B arrester (lightning current arrester) with encapsulated arc chopping spark gap, 1-channel. Housing width: 17.5 mm (1 Div.)

More details

Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

Price: $159.17
*This price is per unit and is the net value (not including taxes if applicable).
Up to 35% discount for registered clients.

Request a quote
How it Works

How does the quotation request work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with our price proposals
4 You can directly process the order for the quotation

There are several options for payment
- Credit card
- Wire Transfer
- PayPal

More info


Height88.6 mm
Width17.6 mm
Depth66.2 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %


IEC power supply systemTN-S
Housing materialPA 6.6
Flammability rating according to UL 94V-0
Standards for cearances and creepage distancesEN 60664-1
EN 61643-11
Mounting typeDIN rail: 35 mm
TypeRail-mountable module, one-piece
Number of positions1
Surge protection fault messageNone
Direction of action1L-N/PE

Protective circuit

IEC test classificationI
EN typeT1
Nominal voltage UN230/400 V AC (TN)
Maximum continuous operating voltage UC (L-PEN)385 V AC
UT (TOV-proof)350 V (5 sec.)
Nominal frequency fN50 Hz (60 Hz)
Rated load current IL80 A
Residual current IPE≤ 0.1 mA
Standby power consumption PC≤ 35 mVA
Nominal discharge current In (8/20) µs (L-PEN)35 kA
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 5 kV
Voltage protection level Up (L-PEN)≤ 5 kV
Response time tA (L-PE)≤ 100 ns
Max. backup fuse with branch wiring400 A AC (gG)
Max. backup fuse with V-type through wiring80 A AC (gG)
Short-circuit resistance IP with max. backup fuse (effective)25 kA
Short-circuit current rating ISCCR3 kA (260 V AC)
Follow current quenching capacity Ifi (L-PEN)3 kA (260 V AC)
1.5 kA (385 V AC)

Connection, protective circuit

Connection methodScrew connection
Connection type INBiconnect screw terminal block
Connection type OUTBiconnect screw terminal block
Connection methodBiconnect terminal block
Screw threadM5
Tightening torque4.5 Nm
Stripping length14.5 mm
Conductor cross section flexible min.2.5 mm²
Conductor cross section flexible max.25 mm²
Conductor cross section solid min.2.5 mm²
Conductor cross section solid max.35 mm²
Conductor cross section AWG6 ... 2

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

PDF of Type 1 / Class I / B arrester lightning current arrester with encapsul - PHOENIX CONTACT - FLT 35-260 - 2800110

PHOENIX CONTACT-2800110-FLT 35-260English61 KbytesPHOENIX CONTACT-2800110-FLT 35-260

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait

* Required fields