FLT 25-400 2800106 PHOENIX CONTACT Combination type 1/2 protective device View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

FLT 25-400 2800106 PHOENIX CONTACT Combination type 1/2 protective device

FLT 25-400

2800106

PHOENIX_CONTACT

Combination type 1/2 protective device

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $280.01
Unit price: $280.01

Quantity Price
1+$280.01
2+$263.49
3+$263.49
4+$263.49
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2800106
Packing unit1 pc
Catalog pagePage 22 (TT-2011)
GTIN4046356479929
Weight per Piece (excluding packing)180.200 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height90 mm
Width17.7 mm
Depth65.5 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %

General

IEC test classificationI
T1
EN typeT1
IEC power supply systemTN-S
TN-C
TT
Mode of protectionL-PEN
Mounting typeDIN rail: 35 mm
Colorblack
Housing materialPA 6.6
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, one-piece
Number of positions1
Surge protection fault messagenone

Protective circuit

Nominal voltage UN230/400 V AC (TN)
230/400 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC(L-PEN)440 V AC
Rated load current IL80 A
Residual current IPE≤ 0.1 mA
Standby power consumption PC≤ 44 mVA
Nominal discharge current In(8/20) µs (L-PEN)25 kA
Impulse discharge current (10/350) µs (L-PEN), charge12.5 As
Impulse discharge current (10/350) µs (L-PEN), specific energy156 kJ/Ω
Impulse discharge current (10/350) µs (L-PEN), peak current value Iimp25 kA
Follow current interrupt rating Ifi(L-PEN)2.5 kA
Short-circuit current rating ISCCR2.5 kA
Voltage protection level Up(L-PEN)≤ 5 kV
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 5 kV
TOV behavior at UT(L-PEN)440 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
Response time tA(L-PEN)≤ 100 ns
Max. backup fuse with V-type through wiring80 A AC (gG)
Max. backup fuse with branch wiring250 A AC (gG)

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque4.5 Nm
Stripping length14.5 mm
Conductor cross section flexible min.2.5 mm²
Conductor cross section flexible max.25 mm²
Conductor cross section solid min.2.5 mm²
Conductor cross section solid max.35 mm²
Conductor cross section AWG6 ... 2

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.