VIOK 1,5-3D/PE 2718206 PHOENIX CONTACT Motor terminal View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VIOK 1,5-3D/PE 2718206 PHOENIX CONTACT Motor terminal

VIOK 1,5-3D/PE

2718206

PHOENIX_CONTACT

Motor terminal

More details


Modular TBs

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $10.63
Unit price: $10.63

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2718206
Packing unit50 pc
Catalog pagePage 449 (C-1-2017)
GTIN4017918062279
Weight per Piece (excluding packing)27.150 g
Custom tariff number85369010
Country of originPL (Poland)

General

Number of levels4
Number of connections7
Nominal cross section2.5 mm²
Colorgray
Insulating materialPA
Flammability rating according to UL 94V2
Rated surge voltage6 kV
Degree of pollution3
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipation for nominal condition0.77 W (the value is multiplied when connecting multiple levels)
Connection in acc. with standardIEC 60947-7-1/IEC 60947-7-2
Nominal current IN24 A
Maximum load current26 A (with a 2.5 mm² conductor cross section)
Nominal voltage UN400 V (when using EB insertion bridges, the nominal voltage is reduced to 250 V.)
Open side panelNo
Result of surge voltage testTest passed
Surge voltage test setpoint7.3 kV
Result of power-frequency withstand voltage testTest passed
Power frequency withstand voltage setpoint1.89 kV
Checking the mechanical stability of terminal points (5 x conductor connection)Test passed
Result of bending testTest passed
Bending test rotation speed10 rpm
Bending test turns135
Bending test conductor cross section/weight0.2 mm² / 0.2 kg
2.5 mm² / 0.7 kg
4 mm² / 0.9 kg
0.2 mm² / 0.2 kg
2.5 mm² / 0.7 kg
4 mm² / 0.9 kg
0.2 mm² / 0.2 kg
2.5 mm² / 0.7 kg
4 mm² / 0.9 kg
Tensile test resultTest passed
Conductor cross section tensile test0.2 mm²
Tractive force setpoint10 N
Conductor cross section tensile test2.5 mm²
Tractive force setpoint50 N
Conductor cross section tensile test4 mm²
Tractive force setpoint60 N
Result of tight fit on supportTest passed
Tight fit on carrierNS 35
Setpoint1 N
Result of voltage-drop testTest passed
Requirement, voltage drop 2nd level≤ 3.2 mV
Result of temperature-rise testTest passed
Short circuit stability resultTest passed
Conductor cross section short circuit testing2.5 mm²
Short-time current0.3 kA
Conductor cross section short circuit testing4 mm²
Short-time current0.48 kA
Result of thermal testTest passed
Proof of thermal characteristics (needle flame) effective duration30 s
Relative insulation material temperature index (Elec.; UL 746 B)125 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))125 °C
Static insulating material application in cold-40 °C

Dimensions

Width6.2 mm
Length82.5 mm
Height NS 35/7,570 mm
Height NS 35/1577.5 mm

Connection data

NotePlease observe the current carrying capacity of the DIN rails.
Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Conductor cross section flexible, with ferrule without plastic sleeve min.0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.2.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.2.5 mm²
Cross section with insertion bridge, solid max.4 mm²
Cross section with insertion bridge, stranded max.2.5 mm²
Cross section with insertion bridge, solid max.4 mm²
Cross section with insertion bridge, stranded max.2.5 mm²
Stripping length8 mm
Internal cylindrical gageA3
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Standards and Regulations

Connection in acc. with standardCSA
IEC 60947-7-1/IEC 60947-7-2
Flammability rating according to UL 94V2

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.