VAL-MS 320/3+1/FM 2859181 PHOENIX CONTACT Surge voltage arrester combination 4-channel, for mounting on NS 3.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-MS 320/3+1/FM 2859181 PHOENIX CONTACT Surge voltage arrester combination 4-channel, for mounting on NS 3..

VAL-MS 320/3+1/FM

2859181

PHOENIX_CONTACT

Available

Ship on today

Surge voltage arrester combination 4-channel, for mounting on NS 35/7.5, with remote indicator contact as PDT, voltage 230 V AC

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$222.47
2+$217.10
3+$214.44
4+$213.27
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Height99 mm
Width71 mm
Depth58 mm
Horizontal pitch4 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012
IEC test classificationII
T2
EN typeT2
IEC power supply systemTN-S
TT
Number of portsOne
SPD designCombination type
Mode of protectionL-N
L-PE
N-PE
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6
PBT
Pollution degree2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions4
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN240/415 V AC (TN-S)
240/415 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-N)335 V AC
Maximum continuous operating voltage UC (L-PE)335 V AC
Maximum continuous voltage UC (N-PE)260 V AC
Rated load current IL80 A
Residual current IPE≤ 5 µA
Standby power consumption PC≤ 450 mVA
Nominal discharge current In (8/20) µs20 kA
Maximum discharge current Imax (8/20) µs40 kA
Follow current interrupt rating Ifi (N-PE)100 A (260 V)
Short-circuit current rating ISCCR25 kA
Voltage protection level Up (L-N)≤ 1.6 kV
Voltage protection level Up (L-PE)≤ 1.9 kV
Voltage protection level Up (N-PE)≤ 1.5 kV
Residual voltage Ures (L-N)≤ 1.6 kV (at In)
≤ 1.5 kV (at 10 kA)
≤ 1.3 kV (at 5 kA)
≤ 1.1 kV (at 3 kA)
Residual voltage Ures (L-PE)≤ 1.9 kV (at In)
≤ 1.5 kV (at 10 kA)
≤ 1.3 kV (at 5 kA)
≤ 1.2 kV (at 3 kA)
Residual voltage Ures (N-PE)≤ 0.4 kV (at In)
≤ 0.25 kV (at 10 kA)
≤ 0.15 kV (at 5 kA)
≤ 0.1 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE)≤ 1.5 kV
TOV behavior at UT (L-N)415 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
TOV behavior at UT (N-PE)1200 V AC (200 ms / withstand mode)
Response time tA (L-N)≤ 25 ns
Response time tA (N-PE)≤ 100 ns
Max. backup fuse with branch wiring125 A AC (gG)
Max. backup fuse with V-type through wiring80 A AC (gG)

Indicator/remote signaling

Connection nameRemote fault indicator contact
Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
30 V DC
Operating current5 mA AC ... 0.75 A AC
1 A DC
Connection methodScrew connection
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section solid min.0.14 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection methodScrew connection
Conductor cross section flexible min.1.5 mm²
Conductor cross section flexible max.25 mm²
Conductor cross section solid min.1.5 mm²
Conductor cross section solid max.35 mm²
Conductor cross section AWG15 ... 2
Screw threadM5
Tightening torque4.5 Nm
Stripping length16 mm

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-L)640 V AC
Maximum continuous operating voltage MCOV (L-N)320 V AC
Maximum continuous operating voltage MCOV (L-G)320 V AC
Maximum continuous operating voltage MCOV (N-G)260 V AC
Nom. voltage240/415 V AC
Mode of protectionL-L
L-N
L-G
N-G
Power distribution system3Y
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-L)2900 V
Measured limiting voltage MLV (L-N)2030 V
Measured limiting voltage MLV (L-G)2720 V
Measured limiting voltage MLV (N-G)1370 V
Nominal discharge current In (L-L)20 kA
Nominal discharge current In (L-N)20 kA
Nominal discharge current In (L-G)20 kA
Nominal discharge current In (N-G)20 kA

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2859181-VAL-MS 320/3+1/FMEnglish162 KbytesPHOENIX CONTACT-2859181-VAL-MS 320/3+1/FM

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or