Product successfully added to your shopping cart
S-PT-1X2-24DC
2880668
PHOENIX_CONTACT
1
Surge protection device
Trabtech (TT)
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2880668 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 101 (C-4-2017) |
GTIN | 4046356049009 |
Weight per Piece (excluding packing) | 352.520 g |
Custom tariff number | 85363010 |
Country of origin | DE (Germany) |
Ambient temperature (operation) | -40 °C ... 85 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Degree of protection | IP67 |
Housing material | Zinc die-cast, surface bronzed and nickel-plated |
---|---|
Color | silver |
Standards for cearances and creepage distances | IEC 60664-1 |
VDE 0110-1 | |
Mounting type | direct screw connection |
Type | Screw-in module |
Number of positions | 3 |
Direction of action | Line-Line & Line-Earth Ground |
IEC test classification | C1 |
---|---|
C2 | |
C3 | |
D1 | |
Nominal voltage UN | 24 V DC |
Maximum continuous voltage UC | 40 V DC |
28 V AC | |
Rated current | 450 mA (55 °C) |
Operating effective current ICat UC | ≤ 10 µA |
Residual current IPE | ≤ 2 µA |
Nominal discharge current In(8/20) µs (line-line) | 10 kA |
Nominal discharge current In(8/20) µs (line-earth) | 10 kA (per path) |
Nominal discharge current In(8/20) µs (shield-earth) | 10 kA (optional) |
Pulse discharge current Iimp(10/350) µs | 1 kA |
Total discharge current Itotal(8/20) µs | 20 kA |
Total discharge current Itotal(10/350) µs | 2 kA |
Max. discharge current Imax(8/20) µs maximum (line-line) | 10 kA |
Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA (per path) |
Max. discharge current Imax(8/20) µs maximum (shield-earth) | 10 kA |
Nominal pulse current Ian (10/1000) µs (line-line) | 23 A |
Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A |
Nominal pulse current Ian (10/1000) µs (Shield-Earth) | 100 A |
Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 55 V |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V (Direct grounding) |
Output voltage limitation at 1 kV/µs (shield-earth) spike | ≤ 600 V (optional) |
Output voltage limitation at 1 kV/µs (line-line) static | ≤ 55 V |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 450 V (Direct grounding) |
Residual voltage at In(line-line) | ≤ 55 V |
Residual voltage with Ian (10/1000) µs (line-line) | ≤ 65 V |
Voltage protection level Up(line-line) | ≤ 80 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up(line-earth) | ≤ 450 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up(shield-ground) | ≤ 600 V (C2 - 10 kV / 5 kA) |
Voltage protection level Upstatic (line-line) | ≤ 50 V (C2 - 10 kV / 5 kA) |
Response time tA(line-line) | ≤ 1 ns |
Response time tA(line-earth) | ≤ 100 ns |
Response time tA (shield-earth) | ≤ 100 ns |
Input attenuation aE, sym. | typ. 0.5 dB (≤ 1.5 MHz / 50 Ω) |
typ. 0.2 dB (≤ 300 kHz / 150 Ω) | |
Cut-off frequency fg (3 dB), sym. in 50 Ohm system | typ. 6 MHz |
Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 2 MHz |
Resistance in series | 2.2 Ω ±10 % |
Surge protection fault message | none |
Max. required back-up fuse | 500 mA (T) |
Impulse durability (line-line) | C2 - 10 kV/5 kA |
D1 - 1 kA | |
Impulse durability (line-earth) | C2 - 10 kV/5 kA |
D1 - 1 kA | |
Impulse durability (shield-earth) | C2 - 10 kV / 5 kA |
D1 - 1 kA |
Connection method | Screw connection |
---|---|
Connection method IN | Screw terminal blocks |
Connection method OUT | Connection line |
Connection technology | Screw connection |
Screw thread | M3 |
Tightening torque | 0.6 Nm |
Stripping length | 6 mm |
Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
Conductor cross section AWG | 26 ... 16 |
China RoHS | Environmentally Friendly Use Period = 50 |
---|---|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX PROTECTION EN.pdf | 27 Mbytes | |
PHOENIX CONTACT-2880668-S-PT-1X2-24DC | 117 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.