S-PT-1X2-24DC 2880668 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

S-PT-1X2-24DC 2880668 PHOENIX CONTACT Surge protection device

S-PT-1X2-24DC

2880668

PHOENIX_CONTACT

Surge protection device

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $220.75
Unit price: $220.75

Quantity Price
1+$220.75
2+$195.66
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2880668
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 101 (C-4-2017)
GTIN4046356049009
Weight per Piece (excluding packing)352.520 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height33.5 mm
Width33.5 mm
Depth137 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Degree of protectionIP67

General

Housing materialZinc die-cast, surface bronzed and nickel-plated
Colorsilver
Standards for cearances and creepage distancesIEC 60664-1
VDE 0110-1
Mounting typedirect screw connection
TypeScrew-in module
Number of positions3
Direction of actionLine-Line & Line-Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC40 V DC
28 V AC
Rated current450 mA (55 °C)
Operating effective current ICat UC≤ 10 µA
Residual current IPE≤ 2 µA
Nominal discharge current In(8/20) µs (line-line)10 kA
Nominal discharge current In(8/20) µs (line-earth)10 kA (per path)
Nominal discharge current In(8/20) µs (shield-earth)10 kA (optional)
Pulse discharge current Iimp(10/350) µs1 kA
Total discharge current Itotal(8/20) µs20 kA
Total discharge current Itotal(10/350) µs2 kA
Max. discharge current Imax(8/20) µs maximum (line-line)10 kA
Max. discharge current Imax(8/20) µs maximum (line-earth)10 kA (per path)
Max. discharge current Imax(8/20) µs maximum (shield-earth)10 kA
Nominal pulse current Ian (10/1000) µs (line-line)23 A
Nominal pulse current Ian (10/1000) µs (line-earth)100 A
Nominal pulse current Ian (10/1000) µs (Shield-Earth)100 A
Output voltage limitation at 1 kV/µs (line-line) spike≤ 55 V
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 450 V (Direct grounding)
Output voltage limitation at 1 kV/µs (shield-earth) spike≤ 600 V (optional)
Output voltage limitation at 1 kV/µs (line-line) static≤ 55 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 450 V (Direct grounding)
Residual voltage at In(line-line)≤ 55 V
Residual voltage with Ian (10/1000) µs (line-line)≤ 65 V
Voltage protection level Up(line-line)≤ 80 V (C2 - 10 kV / 5 kA)
Voltage protection level Up(line-earth)≤ 450 V (C2 - 10 kV / 5 kA)
Voltage protection level Up(shield-ground)≤ 600 V (C2 - 10 kV / 5 kA)
Voltage protection level Upstatic (line-line)≤ 50 V (C2 - 10 kV / 5 kA)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Response time tA (shield-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.5 dB (≤ 1.5 MHz / 50 Ω)
typ. 0.2 dB (≤ 300 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm systemtyp. 6 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 2 MHz
Resistance in series2.2 Ω ±10 %
Surge protection fault messagenone
Max. required back-up fuse500 mA (T)
Impulse durability (line-line)C2 - 10 kV/5 kA
D1 - 1 kA
Impulse durability (line-earth)C2 - 10 kV/5 kA
D1 - 1 kA
Impulse durability (shield-earth)C2 - 10 kV / 5 kA
D1 - 1 kA

Connection data

Connection methodScrew connection
Connection method INScrew terminal blocks
Connection method OUTConnection line
Connection technologyScrew connection
Screw threadM3
Tightening torque0.6 Nm
Stripping length6 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG26 ... 16

Standards and Regulations

Standards/specificationsIEC 61643-21 2002

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.