CT 10-2PE/FS-24 2807955 PHOENIX CONTACT LSA-PLUS plug (COMTRAB CT 10) with surge voltage coarse and fine pro.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

CT 10-2PE/FS-24 2807955 PHOENIX CONTACT LSA-PLUS plug (COMTRAB CT 10) with surge voltage coarse and fine pro..

CT 10-2PE/FS-24

2807955

PHOENIX_CONTACT

Available

Ship on today

LSA-PLUS plug (COMTRAB CT 10) with surge voltage coarse and fine protection for 10 floating signal circuits. Nominal voltage: 24 V DC/AC version: 10 double wires

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection for measurement and control technology - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$413.94
2+$405.98
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Height22 mm
Width111 mm
Depth68.5 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 75 °C
Degree of protectionIP20

General

Housing materialPBT
Flammability rating according to UL 94V0
Colorblack
Standards for cearances and creepage distancesVDE 0110-1
IEC 60664-1
Mounting typeOn CT-TERMIBLOCK and LSA-PLUS disconnect strip
TypeLSA-PLUS module
Direction of actionLine-Line & Line-Earth Ground
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.00

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC40 V DC
28 V AC
Maximum continuous voltage UC (wire-wire)40 V DC
Nominal current IN1.5 A (75°C)
Operating effective current IC at UC≤ 5 µA (a-b)
Residual current IPE≤ 1 µA (per path)
Nominal discharge current In (8/20) µs (Core-Core)119 A (25 °C)
Nominal discharge current In (8/20) µs (Core-Earth)5 kA
Total surge current (8/20) µs10 kA
Max. discharge current Imax (8/20) µs maximum (Core-Core)119 A (25 °C)
Max. discharge current Imax (8/20) µs maximum (Core-Earth)5 kA
Nominal pulse current Ian (10/1000) µs (Core-Core)23 A (25 °C)
Output voltage limitation at 1 kV/µs (Core-Core) spike≤ 70 V
Output voltage limitation at 1 kV/µs (Core-Earth) spike≤ 650 V
Output voltage limitation at 1 kV/µs (Core-Core) static≤ 60 V
Output voltage limitation at 1 kV/µs (Core-Earth) static≤ 650 V
Residual voltage at In (conductor-conductor)≤ 85 V
Residual voltage with Ian (10/1000)µs (conductor-conductor)≤ 65 V
Response time tA (Core-Core)≤ 1 ns
Response time tA (Core-Earth)≤ 100 ns
Input attenuation aE, sym.0.1 dB (Typ. up to 2 MHz / 50 Ω)
0.1 dB (Typ. up to 1 MHz / 150 Ω)
0.1 dB (Typ. up to 400 kHz / 600 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm system10 MHz (typ.)
Cut-off frequency fg (3 dB), sym. in 150 Ohm system4 MHz (typ.)
Cut-off frequency fg (3 dB), sym. in 600 Ohm system1 MHz (typ.)
Capacity (Core-Core)1.1 nF (f=1 MHz / VR= 0 V)
Capacity (Core-Earth)1 pF
Surge protection fault messageNone
Impulse durability (conductor-ground)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 100 A
D1 - 2,5 kA

Connection data

Connection methodcan be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips
Connection type INCOMTRAB plug-in system
Connection type OUTCOMTRAB plug-in system

Standards and Regulations

Standards/regulationsIEC 61643-21

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2807955-CT 10-2PE/FS-24English110 KbytesPHOENIX CONTACT-2807955-CT 10-2PE/FS-24

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or