PT-IQ-2X1+F-48DC-PT 2801250 PHOENIX CONTACT Surge protection, consisting of protective plug and base element.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PT-IQ-2X1+F-48DC-PT 2801250 PHOENIX CONTACT Surge protection, consisting of protective plug and base element..

PT-IQ-2X1+F-48DC-PT

2801250

PHOENIX_CONTACT

Available

Ship on today

Surge protection, consisting of protective plug and base element, with integrated multi-stage status indicator on the module for two signal wires with common reference potential. Indirect grounding via gas-filled surge arrester.

More details


TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection for measurement and control technology - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$181.77
2+$177.13
3+$174.84
4+$173.37
5+$172.81
*This price is per unit and is the net value (not including taxes if applicable).

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Height109.3 mm
Width17.7 mm
Depth77.5 mm
Horizontal pitch1 Div.

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorjet black RAL 9005
Mounting typeDIN rail: 35 mm
TypeDIN rail module, two-section, divisible
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN48 V DC
Maximum continuous voltage UC53 V DC
37 V AC
Nominal current IN300 mA
Operating effective current IC at UC≤ 6 µA (per path)
Residual current IPE≤ 1 µA
Nominal discharge current In (8/20) µs (Core-Earth)10 kA
Nominal discharge current In (8/20) µs (Core-GND)10 kA
Pulse discharge current Iimp (10/350) µs (core-ground)2.5 kA
Impulse discharge current (10/350)˽µs, peak value limp2.5 kA
Voltage protection level Up (core-ground)≤ 750 V (C1 - 1 kV/500 A)
≤ 950 V (C2 - 10 kV / 5 kA)
≤ 850 V (C3 - 25 A)
Voltage protection level Up (core-GND)≤ 105 V (C1 - 1 kV/500 A)
≤ 160 V (C2 - 10 kV / 5 kA)
≤ 90 V (C3 - 25 A)
Voltage protection level Up static (core-ground)≤ 200 V (C2 - 10 kV / 5 kA)
Response time tA (Core-Earth)≤ 1 ns
≤ 100 ns
Input attenuation aE, asym.typ. 0.3 dB (≤ 530 kHz/150 Ω)
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm systemtyp. 1.9 MHz
Capacity (Core-GND)typ. 1.5 nF
Resistance in series1.2 Ω ±5 %
Surge protection fault messageOptical, multi-stage
Max. required back-up fuse315 mA (FF)
Impulse durability (conductor-ground)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C2 - 10 kA
C3 - 25 A
D1 - 2,5 kA
Impulse durability (conductor-GND)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C2 - 10 kA
C3 - 25 A
D1 - 2.5 kA
Pulse reset time (conductor-ground)≤ 250 ms
Pulse reset time (conductor-GND)≤ 1500 ms

Connection data

Connection methodPush-in connection
Connection type INPush-in connection
Connection type OUTPush-in connection
Stripping length10 mm
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12

Connection, equipotential bonding

Connection methodNS 35 DIN rail or connection terminal block