VAL-MS-T1/T2 600DC-PV/2+V-FM 2801164 PHOENIX CONTACT Lightning/surge arrester for 2-pos. isolated 600 V DC v.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-MS-T1/T2 600DC-PV/2+V-FM 2801164 PHOENIX CONTACT Lightning/surge arrester for 2-pos. isolated 600 V DC v..

VAL-MS-T1/T2 600DC-PV/2+V-FM

2801164

PHOENIX_CONTACT

Available

Ship on today

Lightning/surge arrester for 2-pos. isolated 600 V DC voltage systems, for DIN rail mounting, 3-pos. base element with remote indication contact, three plug-in temperature-monitored protective elements, status message on each plug.

More details


Programmable Logic Controllers Plcs

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$201.87
2+$196.88
3+$194.41
4+$192.83
5+$192.82
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Height99 mm
Width53.4 mm
Depth65.5 mm
Horizontal pitch3 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)60g (Half sine/11 ms/3x XYZ)
Vibration (operation)7.5g (5-500 Hz/2.5 h/XYZ)

General

Standards/specificationsEN 50539-11 2013
IEC test classificationPV T1
PV T2
T1
I
EN typeT1
Number of portsOne
SPD failure behaviorOCM (Open-circuit mode)
Connection configurationY configuration
SPD designCombination type
Installation locationInside
AccessibilityAccessible
Installation location of the disconnect deviceInternal
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6-FR
PBT-FR
Pollution degree2
Distance between live and grounded parts8 mm
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Surge protection fault messageOptical, remote indicator contact

Additional descriptions

NoteThe device is intended for touch proof installation in a housing. Ensure that there is a gap of at least 8 mm between the active and grounded parts in the connection area.

Protective circuit DC voltage side (DC)

Maximum continuous operating voltage UCPV720 V DC
Open circuit voltage UOCSTC≤ 600 V DC
Short-circuit current rating ISCPV1000 A
Continuous operating current ICPV< 20 µA
Rated load current IL80 A
Residual current IPE≤ 20 µA DC
≤ 350 A AC
Standby power consumption PC≤ 25 mVA
Nominal discharge current (8/20) µs15 kA
Nominal discharge current In (8/20) µs (L+) - (L-)15 kA
Nominal discharge current In (8/20) µs (L+) - PE15 kA
Nominal discharge current In (8/20) µs (L-) - PE15 kA
Maximum discharge current Imax (8/20) µs40 kA
Maximum discharge current Imax (8/20) µs (L+) - (L-)40 kA
Maximum discharge current Imax (8/20) µs (L+) - PE40 kA
Maximum discharge current Imax (8/20) µs (L-) - PE40 kA
Impulse discharge current (10/350)˽µs, charge2.5 As
Impulse discharge current (10/350)˽µs, specific energy6.25 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp5 kA
Impulse discharge current (10/350)˽µs, charge2.5 As
Impulse discharge current (10/350)˽µs, specific energy6.25 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp5 kA
Impulse discharge current (10/350)˽µs, charge2.5 As
Impulse discharge current (10/350)˽µs, specific energy6.25 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp5 kA
Total discharge current ITotal (8/20) µs40 kA
Total discharge current ITotal (10/350) µs7 kA
Voltage protection level Up (L+) - (L-)≤ 2.6 kV
Voltage protection level Up (L+) - PE≤ 2.6 kV
Voltage protection level Up (L-) - PE≤ 2.6 kV
Residual voltage Ures (L+) - (L-)≤ 2.6 kV (at In)
≤ 2 kV (at 5 kA)
≤ 2.3 kV (at 10 kA)
≤ 2.8 kV (at 20 kA)
≤ 3.1 kV (at 30 kA)
≤ 3.6 kV (at 40 kA)
Residual voltage Ures (L+) - PE≤ 2.6 kV (at In)
≤ 2 kV (at 5 kA)
≤ 2.3 kV (at 10 kA)
≤ 2.8 kV (at 20 kA)
≤ 3.1 kV (at 30 kA)
≤ 3.6 kV (at 40 kA)
Residual voltage Ures (L-) - PE≤ 2.6 kV (at In)
≤ 2 kV (at 5 kA)
≤ 2.3 kV (at 10 kA)
≤ 2.8 kV (at 20 kA)
≤ 3.1 kV (at 30 kA)
≤ 3.6 kV (at 40 kA)
Response time tA (L+) - (L-)≤ 25 ns
Response time tA (L+) - PE≤ 25 ns
Response time tA (L-) -PE≤ 25 ns
Insulation resistance Riso> 5 GΩ (at 500 V DC)

Indicator/remote signaling

Connection nameRemote fault indicator contact
Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
125 V AC (UL)
30 V DC
Operating current5 mA AC ... 1.5 A AC
1 A AC (UL)
1 A DC
Connection methodScrew connection
Screw threadM2
Tightening torque0.25 Nm
4 lbf-in. (UL)
Stripping length7 mm
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section solid min.0.14 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section AWG28 ... 16
30 ... 14 (UL)

Connection data

Connection methodScrew connection
Conductor cross section flexible min.1.5 mm²
Conductor cross section flexible max.25 mm²
Conductor cross section solid min.1.5 mm²
Conductor cross section solid max.35 mm²
Conductor cross section AWG15 ... 2
10 ... 2 (UL)
Screw threadM5
Tightening torque4.5 Nm
30 lbf-in. (UL)
Stripping length16 mm
Connection methodBiconnect terminal blocks
Conductor cross section flexible min.1.5 mm²
Conductor cross section flexible max.16 mm²
Screw threadM5

UL specifications

SPD Type4 (for Type 2 photovoltaic applications)
Maximum continuous operating voltage MCOV (L+) - (L-)720 V DC
Maximum continuous operating voltage MCOV (L+) - G720 V DC
Maximum continuous operating voltage MCOV (L-) - G720 V DC
Nom. voltage600 V AC
Mode of protection(L+) - (L-)
(L+) - G
(L-) - G
Power distribution system1
Voltage protection rating VPR (L+) - (L-)2.5 kV
Voltage protection rating VPR (L+) - G2.5 kV
Voltage protection rating VPR (L-) -G2.5 kV
Nominal discharge current In (L+) - (L-)20 kA
Nominal discharge current In (L+) - G20 kA
Nominal discharge current In (L-) - G20 kA

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2801164-VAL-MS-T1/T2 600DC-PV/2+V-FMEnglish131 KbytesPHOENIX CONTACT-2801164-VAL-MS-T1/T2 600DC-PV/2+V-FM

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or