PSR-SPP- 24UC/ESA2/4X1/1X2/B 2963954 PHOENIX CONTACT Safety relay for emergency stop and safety door up to S.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PSR-SPP- 24UC/ESA2/4X1/1X2/B 2963954 PHOENIX CONTACT Safety relay for emergency stop and safety door up to S..

PSR-SPP- 24UC/ESA2/4X1/1X2/B

2963954

PHOENIX_CONTACT

Available

Ship on today

Safety relay for emergency stop and safety door up to SIL 1, SIL CL 1, Cat. 1, PL c, depending on the application up to SIL 3, SIL CL 3, Cat. 4, PL e, single-channel operation, 4 enabling current paths, nominal input voltage of 24 V AC/DC, plug-in spring-cage terminal block

More details


Safety

INTERFACE Signal converters, switching devices, and power supply units - PHOENIX CONTACT

Relays and security module and speed control. Safety - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$166.27
2+$161.91
3+$159.76
4+$158.38
6+$157.38
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Width22.5 mm
Height112 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 65 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 70 °C
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Shock15g
Vibration (operation)10 Hz ...150 Hz, 2g
Maximum altitude≤ 2000 m (Above sea level)

Input data

Rated control circuit supply voltage US24 V AC/DC -15 % / +10 %
Power consumption at UStyp. 3.36 W (AC)
typ. 1.56 W (DC)
Rated control supply current IStyp. 140 mA AC
typ. 65 mA DC
Typical inrush current2 A (Δt = 10 µs at Us)
Current consumption< 50 mA (with Us/Ix to S12)
0 mA (with Us/Ix to S34)
Voltage at input/start and feedback circuit24 V DC -15 % / +10 %
Typical response time< 65 ms (automatic start)
< 40 ms (manual start)
Typical pick-up time< 65 ms (when controlled via A1)
Typical release time< 45 ms (when controlled via S12)
< 200 ms (when controlled via A1)
Concurrence input 1/2
Recovery time< 1 s
Status display2 x green LEDs
Maximum switching frequency1 Hz
Max. permissible overall conductor resistanceapprox. 22 Ω (Input and start circuits at UN)
Filter time2 ms (at A1 in the event of voltage dips at Us)
max. 1.5 ms (at S12; test pulse width)
min. 7.5 ms (at S12; test pulse rate)
Test pulse rate = 5 x Test pulse width

Output data

Contact type4 enabling current paths
1 signaling current path
Contact materialAgSnO2
Minimum switching voltage15 V AC/DC
Maximum switching voltage250 V AC/DC
Limiting continuous current6 A (N/O contact)
6 A (N/C contact)
Inrush current, minimum25 mA
Maximum inrush current6 A
Sq. Total current72 A2 (see to derating)
Interrupting rating (ohmic load) max.144 W (24 V DC, τ = 0 ms, N/C contact 51/52: 72 W)
288 W (48 V DC, τ = 0 ms, N/C contact 51/52: 144 W)
110 W (110 V DC, τ = 0 ms)
88 W (220 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms, N/C contact 51/52: 750 VA)
Maximum interrupting rating (inductive load)42 W (24 V DC, τ = 40 ms)
42 W (48 V DC, τ = 40 ms)
42 W (110 V DC, τ = 40 ms)
42 W (220 V DC, τ = 40 ms)
42 W (250 V AC, τ = 40 ms)
Switching capacity min.0.4 W
Output fuse10 A gL/gG (N/O contact)
6 A gL/gG (N/C contact)

General

Relay typeElectromechanical relay with forcibly guided contacts in accordance with EN 50205
Mechanical service life10 x 106 cycles
Net weight194.38 g
Mounting typeDIN rail mounting
Assembly instructionsSee derating curve
Degree of protectionIP54
IP20
Min. degree of protection of inst. locationIP54
Mounting positionvertical or horizontal
Controlsingle-channel
Parameters as per EN ISO 138491 (up to Cat. 4 depending on the application)
Stop category0
Parameters for IEC 615081
Housing materialPBT

Connection data

Connection methodSpring-cage connection
pluggableYes
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2963954-PSR-SPP- 24UC/ESA2/4X1/1X2/BEnglish184 KbytesPHOENIX CONTACT-2963954-PSR-SPP- 24UC/ESA2/4X1/1X2/B

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or