Product successfully added to your shopping cart
PSR-MC40-3NO-1DO-24DC-SC
2700569
PHOENIX_CONTACT
1
Safety relays
Safety
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2700569 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 255 (C-6-2017) |
GTIN | 4046356912570 |
Weight per Piece (excluding packing) | 177.000 g |
Custom tariff number | 85371098 |
Country of origin | DE (Germany) |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
---|
Ambient temperature (operation) | -40 °C ... 55 °C (observe derating) |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Maximum altitude | ≤ 2000 m (Above sea level) |
Rated control circuit supply voltage US | 24 V DC -15 % / +10 % |
---|---|
20.4 V DC ... 26.4 V DC | |
Rated control supply current IS | typ. 80 mA |
Power consumption at US | typ. 1.92 W |
Inrush current | 5 A (Δt = 200 µs at Us) |
Filter time | 1 ms (at A1 in the event of voltage dips at Us) |
Protective circuit | Surge protection Suppressor diode |
Protection against polarity reversal for rated control circuit supply voltage |
Input voltage range "0" signal | 0 V DC ... 5 V DC (for safe Off; at S12 and S22) |
---|---|
Input current range "0" signal | 0 mA ... 2 mA (for safe Off; at S12 and S22) |
Inrush current | < 20 mA (with Us/Ixto S12) |
< 200 mA (with Us/Ixto S34) | |
< 5 mA (with Us/Ixto S22) | |
Current consumption | < 5 mA (with Us/Ixto S12) |
< 5 mA (with Us/Ixto S22) | |
> -5 mA (with Us/Ixto S34) | |
< 10 mA (with Us/Ixto S34) | |
Filter time | max. 1.5 ms (at S12, S22; test pulse width) |
min. 7.5 ms (at S12, S22; test pulse rate) | |
Test pulse rate = 5 x Test pulse width | |
Voltage at input/start and feedback circuit | 24 V DC -15 % / +10 % |
Max. permissible overall conductor resistance | 150 Ω |
Output name | Enabling current path |
---|---|
Output description | safety-related N/O contacts |
Number of outputs | 3 (undelayed) |
Contact type | 3 enabling current paths |
Contact material | AgSnO2 |
Switching voltage | min. 12 V AC/DC |
max. 250 V AC/DC (Observe the load curve) | |
Limiting continuous current | 6 A (observe derating) |
Inrush current | min. 3 mA |
max. 6 A | |
Sq. Total current | 48 A2(observe derating) |
Switching capacity | min. 60 mW |
Switching frequency | 0.5 Hz |
Mechanical service life | 10x 106cycles |
Output fuse | 6 A gL/gG (N/O contact) |
4 A gL/gG (for low-demand applications) |
Output description | non-safety-related |
---|---|
Number of outputs | 1 (digital, PNP) |
Voltage | 22 V DC (Us- 2 V) |
Current | max. 100 mA |
Maximum inrush current | 500 mA (Δt = 1 ms at Us) |
Short-circuit protection | no |
Typical pickup time at US | < 250 ms (when controlled via A1) |
---|---|
Typical response time at US | < 175 ms (automatic start) |
< 175 ms (manual, monitored start) | |
Typical release time at US | < 20 ms (when controlled via A1 or S12 and S22.) |
Recovery time | < 500 ms |
Relay type | Electromechanical relay with forcibly guided contacts in accordance with IEC/EN 61810-3 (EN 50205) |
---|---|
Nominal operating mode | 100% operating factor |
Net weight | 177 g |
Mounting position | vertical or horizontal |
Mounting type | DIN rail mounting |
Assembly instructions | See derating curve |
Degree of protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Housing material | PBT |
Housing color | yellow |
Operating voltage display | 1 x green LED |
Status display | 3 x green LED |
Connection method | Screw connection |
---|---|
pluggable | Yes |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Stop category | 0 |
---|---|
Designation | IEC 61508 - High demand |
Safety Integrity Level (SIL) | 3 |
Designation | IEC 61508 - Low demand |
Safety Integrity Level (SIL) | 3 |
Designation | EN ISO 13849 |
Performance level (PL) | e (4 A DC13; 5 A AC15; 8760 switching cycles/year) |
Category | 4 |
Designation | EN 62061 |
Safety Integrity Level Claim Limit (SIL CL) | 3 |
Designation | Air clearances and creepage distances between the power circuits |
---|---|
Standards/regulations | DIN EN 50178 |
Rated insulation voltage | 250 V AC |
250 V AC | |
Rated surge voltage/insulation | Safe isolation, reinforced insulation 6 kV between input circuit and enabling current path (13/14) and enabling current path (23/24) and enabling current path (33/34) Basic insulation 4 kV between all current paths and housing |
Degree of pollution | 2 |
Overvoltage category | III |
Shock | 15g |
Vibration (operation) | 10 Hz ... 150 Hz, 2g |
Conformance | CE-compliant |
China RoHS | Environmentally Friendly Use Period = 50 |
---|---|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX AUTOMATION EN.pdf | 35 Mbytes | |
PHOENIX CONTACT-2700569-PSR-MC40-3NO-1DO-24DC-SC | 137 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.