ELR W3-230AC/500AC- 9I 2297060 PHOENIX CONTACT "4 in 1" three-phase semiconductor reversing contactor with 2.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

ELR W3-230AC/500AC- 9I 2297060 PHOENIX CONTACT "4 in 1" three-phase semiconductor reversing contactor with 2..

ELR W3-230AC/500AC- 9I

2297060

PHOENIX_CONTACT

Available

Ship on today

"4 in 1" three-phase semiconductor reversing contactor with 230 V AC input, 9 A output current, emergency stop function, and adjustable overload switching.

More details


Programmable Logic Controllers Plcs

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$157.03
2+$152.86
3+$150.79
4+$149.46
6+$148.27
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Input data

Input nameDevice supply
Mains frequency40 Hz
100 Hz
Rated control circuit supply voltage US230 V AC
Voltage range with reference to US0.4 ... 1.1
Rated control supply current IS4 mA
Rated actuating voltage UC230 V AC
Voltage range with reference to UC0.4 ... 1.1
Rated actuating current IC7 mA
Protective circuitSurge protection
Typical response time< 35 ms
Typical turn-off time< 80 ms
Operating voltage displayGreen LED
Status displayYellow LED
IndicationRed LED
Input nameControl input right/left
Switching threshold44 V AC (“0” signal)
85 V AC (“1” signal)

Output data load output

Nominal output voltage500 V AC
Nominal output voltage range42 V AC ... 550 V AC
Load current range1.5 A ... 9 A (see to derating)
Rated operating current at AC-519 A
Rated operating current at AC-53a6.5 A
Leakage current0 mA
Residual voltage< 0.5 V
Surge current100 A (t = 10 ms)
Protective circuitSurge protection

Output data reply output

NoteConfirmation 01: Floating PDT contact

Measuring technology and signaling contact

Measuring viaCurrent transformer for line current on L1 and L3
Current range1 A ... 45 A

Connection data, control circuit

Connection nameControl circuits
Connection methodScrew connection
Stripping length8 mm
Screw threadM3
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14

General

Test voltage input/output4 kVrms
Mounting positionVertical (horizontal DIN rail)
Assembly instructionsCan be aligned with spacing = 20 mm
Operating mode100% operating factor
DesignationStandards/regulations
Standards/regulationsDIN EN 50178
EN 60947
DesignationPower station requirements
Standards/regulationsDWR 1300 / ZXX01/DD/7080.8d
DesignationAir clearances and creepage distances between the power circuits
Standards/regulationsDIN EN 50178
Insulationsafe isolation
Pollution degree2
Overvoltage categoryIII
Reversing frequency≤ 2 Hz

Dimensions

Width22.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Degree of protectionIP20

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2297060-ELR W3-230AC/500AC- 9IEnglish148 KbytesPHOENIX CONTACT-2297060-ELR W3-230AC/500AC- 9I

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or