MACX MCR-SL-RPSSI-I-UP 2865968 PHOENIX CONTACT Repeater power supply for supplying 2 and 3-conductor transmi.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MACX MCR-SL-RPSSI-I-UP 2865968 PHOENIX CONTACT Repeater power supply for supplying 2 and 3-conductor transmi..

MACX MCR-SL-RPSSI-I-UP

2865968

PHOENIX_CONTACT

Available

Ship on today

Repeater power supply for supplying 2 and 3-conductor transmitters with HART transmission and wide range power supply, SIL, screw connection

More details


Programmable Logic Controllers Plcs

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$243.46
2+$237.71
3+$234.86
4+$234.12
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Width17.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Maximum altitude≤ 2000 m
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Degree of protectionIP20

Input data

Signal inputRepeater power supply operation
Current input signal4 mA ... 20 mA
Transmitter supply voltage> 16 V (20 mA)
> 15.3 V (22.5 mA)
Signal inputSignal conditioner operation
Current input signal0 mA ... 20 mA
4 mA ... 20 mA

Output data

Signal outputRepeater power supply operation
Voltage output signal1 V ... 5 V (internal resistance, 250 Ω, 0.1%)
Current output signal4 mA ... 20 mA (active)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Transmission Behavior1:1 to input signal
Load/output load current output< 600 Ω (20 mA)
< 525 Ω (22.5 mA)
Output ripple< 20 mVrms
Output behavior in the event of an error0 mA (Cable break in the input)
≥ 22.5 mA (Cable short-circuit in the input)
Signal outputSignal conditioner operation
Voltage output signal0 V ... 5 V (internal resistance, 250 Ω, 0.1%)
Current output signal0 mA ... 20 mA (active)
4 mA ... 20 mA (active)
0 mA ... 20 mA (14 ... 26 V ext. source voltage)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Load/output load current output< 600 Ω (20 mA)
< 525 Ω (22.5 mA)
Output ripple< 20 mVrms
Output behavior in the event of an error0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)

Power supply

DesignationRepeater power supply operation
Supply voltage range24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Max. current consumption< 80 mA (24 V DC / 20 mA)
Power consumption< 1.6 W (24 V DC/ 20 mA)
< 1.9 W

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length7 mm
Screw threadM3
Connection methodScrew connection
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

General

No. of channels1
Maximum transmission error< 0.1 % (of final value)
Transmission error, typical< 0.05 % (of final value)
Maximum temperature coefficient< 0.01 %/K
Step response (10-90%)< 600 µs (for 4 mA ... 20 mA step)
Status displayGreen LED (supply voltage)
Flammability rating according to UL 94V0
Pollution degree2
Overvoltage categoryII
Emitted interferenceEN 61000-6-4
Housing materialPA 66-FR
Colorgreen
DesignationInput/output/power supply
Electrical isolation300 Vrms (Rated insulation voltage (overvoltage category II; pollution degree 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
ConformanceCE-compliant, additionally EN 61326-1
ATEXEx II 3 G Ex nA IIC T4 Gc X
UL, USA / CanadaUL 508 Listed
UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
Functional Safety (SIL)SIL 2

Data communication (bypass)

HART functionYes
Protocols supportedHART

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2865968-MACX MCR-SL-RPSSI-I-UPEnglish162 KbytesPHOENIX CONTACT-2865968-MACX MCR-SL-RPSSI-I-UP

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or