PR2-RSP3-LV-120AC/2X21 2834708 PHOENIX CONTACT Relay Module View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PR2-RSP3-LV-120AC/2X21 2834708 PHOENIX CONTACT Relay Module

PR2-RSP3-LV-120AC/2X21

2834708

PHOENIX_CONTACT

5

Relay Module

More details


Industrial Relays

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2834708
Packing unit5 pc
Minimum order quantity5 pc
NoteMade to Order (non-returnable)
Catalog pagePage 395 (C-7-2013)
GTIN4017918996277
Weight per Piece (excluding packing)125.250 g
Custom tariff number85364900
Country of originJP (Japan)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width31 mm
Height95 mm
Depth84 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 70 °C

Coil side

Nominal input voltage UN120 V AC
Typical input current at UN11 mA (at 50 Hz)
9 mA (At 60 Hz)
Typical response time4 ms ... 10 ms
Typical release time range3 ms ... 12 ms
Protective circuitVaristor
Operating voltage displayLED red
Power dissipation for nominal condition1.32 W

Contact side

Contact type2 PDT
Type of switch contactSingle contact
Contact materialAg
Maximum switching voltage250 V AC/DC
Minimum switching voltage5 V
Min. switching current1 mA
Maximum inrush current20 A (15 ms)
Limiting continuous current10 A
Interrupting rating (ohmic load) max.240 W (at 24 V DC)
160 W (at 48 V DC)
110 W (at 60 V DC)
72 W (at 110 V DC)
130 W (at 220 V DC)
2500 VA (for 250 V AC)

General

Test voltage relay winding/relay contact2 kV (50 Hz, 1 min.)
Test voltage relay contact/relay contact2 kV (50 Hz, 1 min.)
Operating mode100% operating factor
Mechanical service life5x 107cycles
Service life, electricalsee diagram
Mounting positionany
Assembly instructionsIn rows with zero spacing
Net weight (SAP)125.25 g

Connection data input side

Connection nameCoil side
Connection methodSpring-cage connection
Stripping length12 mm
Conductor cross section solid0.2 mm² ... 1.5 mm²
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16

Standards and Regulations

Standards/regulationsIEC 60664
EN 50178
Degree of pollution3
Overvoltage categoryII

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Articles in set

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.