PT 4-EX(I)-24DC-ST 2839253 PHOENIX CONTACT Surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PT 4-EX(I)-24DC-ST 2839253 PHOENIX CONTACT Surge protection plug

PT 4-EX(I)-24DC-ST

2839253

PHOENIX_CONTACT

Surge protection plug

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $235.88
Unit price: $235.88

Quantity Price
1+$235.88
2+$214.64
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2839253
Packing unit10 pc
Catalog pagePage 134 (C-4-2017)
GTIN4017918182878
Weight per Piece (excluding packing)26.150 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height45 mm
Width17.7 mm
Depth52 mm
Horizontal pitch1 Div.
Complete module height90 mm
Complete module width17.7 mm
Complete module depth65.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorsky blue RAL 5015
Mounting typeon base element
TypeMale
Number of positions4
Direction of actionLine-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.00

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC30 V DC
21 V AC
Rated current500 mA (40 °C)
Operating effective current ICat UC≤ 5 µA
Residual current IPE≤ 4 µA
Nominal discharge current In(8/20) µs (line-line)308 A
Nominal discharge current In(8/20) µs (line-earth)10 kA
Pulse discharge current Iimp(10/350) µs (line-earth)1 kA
2 kA (in total)
Total discharge current Itotal(8/20) µs20 kA
Total discharge current Itotal(10/350) µs2 kA
Max. discharge current Imax(8/20) µs maximum (line-line)308 A
Max. discharge current Imax(8/20) µs maximum (line-earth)20 kA (in total)
Nominal pulse current Ian (10/1000) µs (line-line)59 A
Output voltage limitation at 1 kV/µs (line-line) spike≤ 45 V
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 1 kV
Output voltage limitation at 1 kV/µs (line-line) static≤ 45 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 1 kV
Residual voltage at In(line-line)≤ 70 V
Residual voltage with Ian (10/1000) µs (line-line)≤ 65 V
Voltage protection level Up(line-line)≤ 60 V (C1 - 500 V / 250 A)
≤ 50 V (C3 - 10 A)
≤ 50 V (C3 - 25 A)
Voltage protection level Up(line-earth)≤ 1 kV (C1 - 1 kV/500 A)
≤ 1 kV (C2 - 2 kV/1 kA)
≤ 1 kV (C2 - 10 kV / 5 kA)
≤ 1 kV (D1 - 1 kA)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.1 dB (≤ 1 MHz / 50 Ω)
typ. 0.1 dB (≤ 500 kHz / 150 Ω)
typ. 0.1 dB (≤ 100 kHz / 600 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm systemtyp. 7 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 2.5 MHz
Cut-off frequency fg (3 dB), sym. in 600 Ohm systemtyp. 600 kHz
Resistance in series0 Ω
Surge protection fault messagenone
Max. required back-up fuse500 mA (T)
Impulse durability (line-line)C1 - 0.5 kV / 250 A
C3 - 10 A
C3 - 25 A
Impulse durability (line-earth)C1 - 1 kV/500 A
C2 - 2 kV/1 kA
C2 - 10 kV/5 kA
D1 - 1 kA
Alternating current carrying capacity (line-earth)5 A - 1 s

Connection data

Connection methodScrew connection (in connection with the base element)
Screw threadM3
Tightening torque0.5 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/specificationsEN 61643-21 A2:2013
EN 60079-0 2012
EN 60079-11 2012
EN 60079-26 2007
IEC 61643-21 A2:2012
IEC 60079-0 2011
IEC 60079-11 2011
IEC 60079-26 2006

General

Maximum inner capacitance Ci1.1 nF
Max. internal inductance Li1 µH
Maximum inner time factor (Ri/Li)≤ 10 µs
Max. input current Ii500 mA (T4 / ≤ 80°C)
500 mA (T5 / ≤ 55 °C)
500 mA (T6 / ≤ 40 °C)
Max. input voltage Ui30 V DC
max. input power Pi850 mW (T4 / ≤ 80°C)
700 mW (T5 / ≤ 55 °C)
700 mW (T6 / ≤ 40 °C)
Ambient temperature (operation)-40 °C ... 80 °C (T4)
-40 °C ... 55 °C (T5)
-40 °C ... 40 °C (T6)

Conformity / approvals

ATEX II 1G Ex ia IIC T4...T6 Ga
 II 1D Ex ia IIIC T135°C...T85°C Da
IECExEx ia IIC T4...T6 Ga
Ex ia IIIC T135 °C...T85 °C Da

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.