PT PE/S+1X2-24-ST 2819008 PHOENIX CONTACT Protective plug PT with surge voltage equipment protection for pow.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PT PE/S+1X2-24-ST 2819008 PHOENIX CONTACT Protective plug PT with surge voltage equipment protection for pow..

PT PE/S+1X2-24-ST

2819008

PHOENIX_CONTACT

10

Available

Ship on today

Protective plug PT with surge voltage equipment protection for power supply units, visual fault warning, nominal voltage: 24 V and a 2-core floating signal circuit, nominal voltage: 24 V.

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection for measurement and control technology - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Height44.8 mm
Width17.5 mm
Depth51.7 mm
Horizontal pitch1 Div.
Complete module height90 mm
Complete module width17.7 mm
Complete module depth65.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorjet black RAL 9005
Mounting typeOn base element
TypeDIN rail module, two-section, divisible
Current supply arrester can be tested with CHECKMASTER starting with software version:From SW rev. 1.00
Direction of actionL-N-PE & Signal Line-Signal Line-Earth Ground

Protective circuit, power supply

IEC test classificationIII
T3
EN typeT3
Arrester rated voltage UC34 V AC
44 V DC
Nominal frequency fN50 Hz (60 Hz)
Nominal current IN6 A (30 °C)
Operating effective current IC at UC≤ 1.5 mA
Residual current IPE≤ 5 µA
Nominal discharge current In (8/20) µs700 A
Max. discharge current Imax (8/20) µs2 kA
Combination wave UOC2 kV
Voltage protection level Up (L-N)≤ 0.18 kV
Voltage protection level Up (L-PE)≤ 0.55 kV
Response time (L-N)≤ 25 ns
Response time (L-PE)≤ 100 ns
Surge protection fault messageoptical

Connection (protective circuit, power supply)

Connection methodPlug
Connection type INPLUGTRAB plug-in system
Connection type OUTPLUGTRAB plug-in system

Protective circuit, information technology

Nominal voltage UN24 V AC
Arrester rated voltage UC40 V DC
28 V AC
Nominal current IN450 mA (45°C)
Operating effective current IC at UC≤ 5 µA
Residual current IPE≤ 2 µA
Nominal discharge current In (8/20) µs (Core-Core)10 kA
Nominal discharge current In (8/20) µs (Core-Earth)20 kA (in total)
Max. discharge current Imax (8/20) µs maximum (Core-Core)10 kA
Max. discharge current Imax (8/20) µs maximum (Core-Earth)20 kA (in total)
Voltage protection level Up (core-core)≤ 80 V (C2 - 10 kV/5 kA)
Voltage protection level Up (core-ground)≤ 450 V (C2 - 10 kV/5 kA)
Response time tA (Core-Core)≤ 1 ns
Response time tA (Core-Earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.5 dB (≤ 1.5 MHz / 50 Ω)
typ. 0.2 dB (≤ 500 kHz / 150 Ω)
typ. 0.1 dB (≤ 100 kHz / 600 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm systemtyp. 8 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 3 MHz
Cut-off frequency fg (3 dB), sym. in 600 Ohm systemtyp. 800 kHz
Capacity (Core-Core)typ. 1.1 nF
Capacity (Core-Earth)typ. 4 pF
Resistance in series2.2 Ω ±10 %
Impulse discharge current (10/350)˽µs, peak value limp2.5 kA
Surge protection fault messageOptical, remote indicator contact
Output voltage limitation at 1 kV/µs (wire-wire)≤ 55 V
Output voltage limitation at 1 kV/µs (wire-earth)≤ 25 V
Residual voltage at In (conductor-conductor)≤ 55 V
Residual voltage with Ian (10/1000)µs (conductor-conductor)≤ 65 V
Impulse durability (conductor-conductor)C2 - 10 kV/5 kA
C3 - 23 A
Impulse durability (conductor-ground)C2 - 10 kV/5 kA
D1 - 2,5 kA

Power supply, general

Connection methodPlug
Connection type INPLUGTRAB plug-in system
Connection type OUTPLUGTRAB plug-in system

Standards (protective circuit, information technology)

IEC test classificationC1
C2
C3

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2819008-PT PE/S+1X2-24-STEnglish122 KbytesPHOENIX CONTACT-2819008-PT PE/S+1X2-24-ST