Protective plug PT with HF protective circuit for two 2-core floating signal circuits. Nominal voltage: 24 V DC

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection for information technology - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Height45 mm
Width17.7 mm
Depth52 mm
Horizontal pitch1 Div.

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialPA
Flammability rating according to UL 94V0
Colorblack
Standards for cearances and creepage distancesDIN VDE 0110-1
IEC 60664-1
Mounting typeOn base element
TypeDIN rail module, two-section, divisible
Number of positions5
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.00

Protective circuit

IEC test classificationC1
C2
C3
D1
VDE requirement classC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC28 V DC
19.8 V AC
Maximum continuous voltage UC (wire-wire)28 V DC
19.8 V AC
Maximum continuous voltage UC (wire-ground)28 V DC (with PT 2x2-BE)
Nominal current IN450 mA (45°C)
Operating effective current IC at UC≤ 5 µA
Residual current IPE≤ 4 µA (with PT 2x2-BE)
≤ 1 µA (with PT 2x2+F-BE)
Nominal discharge current In (8/20) µs (Core-Core)10 kA
Nominal discharge current In (8/20) µs (Core-Earth)10 kA
Total surge current (8/20) µs20 kA
Max. discharge current Imax (8/20) µs maximum (Core-Core)10 kA
Max. discharge current Imax (8/20) µs maximum (Core-Earth)10 kA
Nominal pulse current Ian (10/1000) µs (Core-Core)30 A
Impulse discharge current (10/350)˽µs, peak value limp2.5 kA
Output voltage limitation at 1 kV/µs (Core-Core) spike≤ 120 V
Output voltage limitation at 1 kV/µs (Core-Earth) spike≤ 450 V
≤ 1 kV (with PT 2x2+F-BE)
Output voltage limitation at 1 kV/µs (Core-Core) static≤ 45 V
Output voltage limitation at 1 kV/µs (Core-GND) static≤ 450 V
Residual voltage at In (conductor-conductor)≤ 40 V
Residual voltage with Ian (10/1000)µs (conductor-conductor)≤ 50 V
Voltage protection level Up (core-core)≤ 120 V (C2 - 10 kV / 5 kA)
Voltage protection level Up (core-ground)≤ 450 V (C2 - 10 kV / 5 kA)
Response time tA (Core-Core)≤ 500 ns
Response time tA (Core-Earth)≤ 500 ns
Input attenuation aE, sym.0.2 dB (≤ 5 MHz)
Cut-off frequency fg (3 dB), sym. in 100 Ohm systemtyp. 70 MHz
Capacity (Core-Core)typ. 30 pF
Resistance in series2.2 Ω
Max. required back-up fuse500 mA (e.g. T in acc. with IEC 127-2/III)
Impulse durability (conductor-conductor)C2 - 10 kV/5 kA
Impulse durability (conductor-ground)C2 - 10 kV/5 kA
D1 - 2,5 kA

Connection data

Connection methodScrew connection (in connection with the base element)
Connection type INPLUGTRAB plug-in system
Connection type OUTPLUGTRAB plug-in system
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12

Standards and Regulations

Standards/regulationsIEC 61643-21

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2839729-PT 2X2-HF-24 DC-STEnglish145 KbytesPHOENIX CONTACT-2839729-PT 2X2-HF-24 DC-ST

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or