Key Commercial Data

Orderkey2742638
Packing unit1 pc
Catalog pagePage 255 (AX-2009)
GTIN4017918819347
Weight per Piece (excluding packing)395.000 g
Custom tariff number85389091
Country of originDE (Germany)

Note

Utilization restriction1

Dimensions

Dimensional drawing
Width182.6 mm
Height140.5 mm
Depth71.5 mm

Ambient conditions

Ambient temperature (operation)0 °C ... 55 °C
Permissible humidity (operation)95 % (non-condensing)
Permissible humidity (storage/transport)95 % (non-condensing)
Air pressure (operation)80 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20

General

Mounting typeDIN rail
Net weight395 g
Note on weight specificationswith connectors

Interfaces

DesignationPROFIBUS DP
No. of channels1
Connection methodD-SUB-9 female connector
Transmission speed9.6 kbps ... 12 Mbps
DesignationInline local bus
Connection methodInline data jumper
Transmission speed500 kbps
DesignationSupply
Connection method8-pos. Inline power connector

System limits of the bus coupler

Amount of process datamax. 176 Byte (per station)
max. 176 Byte (Input)
max. 176 Byte (Output)
Number of local bus devices that can be connectedmax. 63
Number of devices with parameter channelmax. 16
Number of supported branch terminals with remote bus branch0

Inline potentials

DesignationBus coupler supply UBC; Communications power UL(7.5 V) and the analog supply UANA(24 V) are generated from the bus coupler supply.
Supply voltage24 V DC (via Inline connector)
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumptiontyp. 100 mA (without connected Inline I/O terminals)
max. 1.25 A (with max. number of connected I/O terminal blocks)
DesignationCommunications power (UL)
Supply voltage7.5 V DC ±5 %
Power supply unitmax. 2 A DC
DesignationSupply of analog modules (UANA)
Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unitmax. 0.5 A DC (observe derating)
DesignationMain circuit supply (UM)
Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unitmax. 8 A DC (sum of UM+ US)
DesignationSegment circuit supply (US)
Supply voltage24 V DC (via voltage jumper)
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unitmax. 8 A DC (sum of UM+ US)

Digital inputs

Input nameDigital inputs
Description of the inputEN 61131-2 type 1
Connection methodSpring-cage connection
Connection technology3-wire
Number of inputs16
Type of protectionPolarity reversal
Input voltage24 V DC
Input voltage range "1" signal15 V DC ... 30 V DC
Typical input current per channeltyp. 3 mA

Digital outputs

Output nameDigital outputs
Connection methodSpring-cage connection
Connection technology3-wire
Number of outputs16
Type of protectionShort-circuit and overload protection
Output voltage24 V DC -1 V (At nominal current)
Nominal output voltage24 V DC
Maximum output current per channel500 mA
Maximum output current per module8 A
Nominal load, inductive12 VA
Nominal load, lamp12 W
Nominal load, ohmic12 W

Electrical isolation

Test sectionRS-485 interface / supply voltage 500 V AC
RS-485 interface / local bus 500 V AC

Standards and Regulations

Mechanical testsVibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation: 25g, 11 ms duration, semi-sinusoidal shock impulse

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.