PT 2-PE/S-24AC/FM 2800457 PHOENIX CONTACT Type 3 surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PT 2-PE/S-24AC/FM 2800457 PHOENIX CONTACT Type 3 surge protection device

PT 2-PE/S-24AC/FM

2800457

PHOENIX_CONTACT

Type 3 surge protection device

More details


Home > PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Go to successor article: PLT-SEC-T3-24-FM-UT 2907916

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2800457
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 56 (C-6-2013)
GTIN4046356547840
Weight per Piece (excluding packing)79.400 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height90 mm
Width17.7 mm
Depth65.5 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 85 °C

General

Housing materialPA
Flammability rating according to UL 94V0
Colorblack
Standards for cearances and creepage distancesIEC 60664-1
TypeDIN rail module, two-section, divisible
Mounting typeDIN rail: 35 mm
Number of positions2
Direction of action1L-N & N-PE

Protective circuit

EN typeT3
Nominal voltage UN24 V AC/DC
Arrester rated voltage UC34 V AC
44 V DC
Nominal frequency fN50 Hz
60 Hz
Nominal current IN26 A (30 °C)
Standby power consumption PC≤ 60 mVA
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (L-N)1 kA
Nominal discharge current In(8/20) µs (L-PE)1 kA
Combination wave UOC2 kV
Voltage protection level Up(L-N)≤ 180 V
Voltage protection level Up(L-PE)≤ 550 V
Residual voltage at In, (L-N)≤ 180 V
Residual voltage at In, (L-PE)≤ 120 V
Response time tA(L-N)≤ 25 ns
Response time tA(L-PE)≤ 100 ns
Max. required back-up fuse25 A (gL)
25 A (MCB B/C)
Short-circuit withstand capability IPwith max. backup fuse (r.m.s.)1.5 kA
Surge protection fault messageOptical, remote indicator contact

Non-heating apparatus connection, power supply

Connection method INScrew terminal blocks
Connection method OUTScrew terminal blocks
Screw threadM3
Tightening torque0.5 Nm
Stripping length8 mm
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12

Remote indication contact

Connection nameRemote fault indicator contact
Switching functionN/C contact
Connection methodScrew connection
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Maximum operating voltage Umax.AC250 V
Maximum operating voltage UmaxDC50 V
Max. operating current Imax3 A AC

Standards and Regulations

Standards/specificationsIEC 61643-1 2005
EN 61643-11/A11 2007
UL 1449 ed. 3

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.