VAL-MS 350 VF/3+0-FM 2901862 PHOENIX CONTACT Plug-in surge arrester free of leakage current for 3-phase powe.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-MS 350 VF/3+0-FM 2901862 PHOENIX CONTACT Plug-in surge arrester free of leakage current for 3-phase powe..

VAL-MS 350 VF/3+0-FM

2901862

PHOENIX_CONTACT

Available

Ship on today

Plug-in surge arrester free of leakage current for 3-phase power supply networks with N and PE in a common conductor (4-conductor system: L1, L2, L3, PEN), with remote indication contact.

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$208.49
2+$203.36
3+$200.82
4+$199.29
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Height99 mm
Width53.4 mm
Depth58 mm
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012
IEC test classificationII
T2
EN typeT2
Lightning protection classII
Number of portsOne
SPD designCombination type
Mode of protectionL-PE
L-PEN
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6
PBT
Pollution degree2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions3
Surge protection fault messageOptical, remote indicator contact

Additional descriptions

NoteOnly usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE = RA accordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a).

Protective circuit

Nominal voltage UN240/415 V AC (TN-C)
230 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC350 V AC
Rated load current IL80 A
Residual current IPE≤ 5 µA
Standby power consumption PC≤ 6 mVA
Nominal discharge current In (8/20) µs10 kA
Maximum discharge current Imax (8/20) µs20 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures≤ 1.2 kV (at In)
≤ 1.2 kV (at 10 kA)
≤ 1.1 kV (at 5 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 1.5 kV
TOV behavior at UT (L-PEN)415 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
Response time tA≤ 100 ns
Max. backup fuse with branch wiring125 A AC (gG)
Max. backup fuse with V-type through wiring80 A AC (gG)

Indicator/remote signaling

Connection nameRemote fault indicator contact
Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
30 V DC
Operating current5 mA AC ... 1.5 A AC
1 A DC
Connection methodScrew connection
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section solid min.0.14 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection methodScrew connection
Conductor cross section flexible min.1.5 mm²
Conductor cross section flexible max.25 mm²
Conductor cross section solid min.1.5 mm²
Conductor cross section solid max.35 mm²
Conductor cross section AWG15 ... 2
Screw threadM5
Tightening torque4.5 Nm
Stripping length16 mm

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-L)700 V AC
Nom. voltage240/350 V AC
Mode of protectionL-L
Power distribution system3D
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-L)2420 V
Nominal discharge current In (L-L)20 kA

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2901862-VAL-MS 350 VF/3+0-FMEnglish131 KbytesPHOENIX CONTACT-2901862-VAL-MS 350 VF/3+0-FM

Reviews (0)