OPT-24DC/230AC/ 1 2967950 PHOENIX CONTACT Miniature solid-state relay View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

OPT-24DC/230AC/ 1 2967950 PHOENIX CONTACT Miniature solid-state relay

OPT-24DC/230AC/ 1

2967950

PHOENIX_CONTACT

10

Miniature solid-state relay

More details


Industrial Relays

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
10+$20.04
20+$19.24
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Often bought together

More info



Key Commercial Data

Orderkey2967950
Packing unit10 pc
Minimum order quantity10 pc
Catalog pagePage 301 (C-5-2017)
GTIN4017918190538
Weight per Piece (excluding packing)5.750 g
Custom tariff number85364190
Country of originJP (Japan)

Dimensions

Width5 mm
Height28 mm
Depth15 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 70 °C

Input data

Nominal input voltage UN24 V DC
Input voltage range in reference to UN0.8 ... 1.2
Input voltage range19.2 V DC ... 28.8 V DC
Switching threshold "0" signal, voltage≤ 5 V
Switching threshold "1" signal voltage≥ 10 V
Typical input current at UN6 mA
Typical response time6 ms (at UN)
Typical turn-off time500 µs (at UN)
Transmission frequency10 Hz
Power dissipation for nominal condition0.07 W

Output data

Output voltage range24 V AC ... 253 V AC
Limiting continuous current0.75 A (see derating curve)
Maximum inrush current30 A (10 ms)
Min. load current10 mA
Leakage current< 1 mA
Max. load value4.5 A2s
Voltage drop at max. limiting continuous current< 1 V
Output circuit2-conductor floating, zero voltage switch
Type of protectionRCV circuit
Protective circuit/componentRCV circuit

General

Test voltage input/output2.5 kV (50 Hz, 1 min.)
Mounting positionany
Assembly instructionsIn rows with zero spacing
Operating mode100% operating factor
Degree of protectionRT III (wash-proof)
DesignationStandards/regulations
Standards/regulationsIEC 60664
EN 50178
Degree of pollution2
Overvoltage categoryIII

Standards and Regulations

Connection in acc. with standardCUL
DesignationStandards/regulations
Standards/regulationsIEC 60664
EN 50178
InsulationBasic insulation
Degree of pollution2
Overvoltage categoryIII

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.