Measuring transducer power supply and input isolating amplifier, HART-transparent. Transfers supplied or active 0/4 - 20 mA electrically isolated signals from the field to two loads. 4-way electrical isolation, SIL 2 according to IEC 61508, push-in Technology

More details


Programmable Logic Controllers Plcs

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$297.49
2+$290.84
3+$288.30
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Width12.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 60 °C (Any mounting position)
-20 °C ... 70 °C (any mounting position, module distance 5 mm, MTBF reduction factor 2.5, not assessed by UL)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Maximum altitude≤ 2000 m
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Degree of protectionIP20

Input data

Signal inputRepeater power supply operation
Current input signal4 mA ... 20 mA
Transmitter supply voltage> 21.5 V (20 mA)
> 21 V (23 mA)
Signal inputSignal conditioner operation
Current input signal0 mA ... 20 mA
4 mA ... 20 mA
Voltage drop< 3.9 V

Output data

Signal outputRepeater power supply operation
Current output signal4 mA ... 20 mA (active)
0 mA ... 20 mA
Load/output load current output< 450 Ω (20 mA)
< 380 Ω (23 mA)
Output ripple< 20 mVrms
Output behavior in the event of an error0 mA (Cable break in the input)
≥ 23 mA (Cable short-circuit in the input)
Signal outputSignal conditioner operation
Current output signal0 mA ... 20 mA (active)
4 mA ... 20 mA (active)
Load/output load current output< 450 Ω (20 mA)
< 380 Ω (23 mA)
Output ripple< 20 mVrms
Output behavior in the event of an error0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)

Power supply

DesignationRepeater power supply operation
Supply voltage range19.2 V DC ... 30 V DC (24 V DC (-20% ... +25%))
Max. current consumption< 75 mA (24 V DC / 20 mA)
Power consumption< 1.45 W (24 V DC/ 20 mA)

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm
Connection methodPush-in connection

General

Maximum transmission error< 0.1 % (of final value)
Transmission error, typical< 0.05 % (of final value)
Maximum temperature coefficient< 0.01 %/K
Step response (10-90%)< 1.3 µs (for 4 mA ... 20 mA step)
Status displayGreen LED (PWR supply voltage)
Flammability rating according to UL 94V0
Emitted interferenceEN 61000-6-4
Housing materialPA 66-FR
Colorgreen
DesignationInput/output/power supply
Electrical isolation300 Vrms (Rated insulation voltage (overvoltage category II; pollution degree 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
DesignationOutput 1/output 2
Electrical isolation1.5 kV AC (50 Hz, 1 min., test voltage)
ConformanceCE-compliant, additionally EN 61326-1
ATEXEx II 3 G Ex nA IIC T4 Gc X
UL, USA / CanadaUL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
Functional Safety (SIL)SIL 2

Data communication (bypass)

HART functionYes
Protocols supportedHART

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value3 %
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value3 %
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value3 %

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2924838-MACX MCR-SL-RPSSI-2I-SPEnglish138 KbytesPHOENIX CONTACT-2924838-MACX MCR-SL-RPSSI-2I-SP

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or