MINI MCR-SL-2CP-I-I 2864655 PHOENIX CONTACT MCR passive isolator, 2-channel, for the electrical isolation of.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MINI MCR-SL-2CP-I-I 2864655 PHOENIX CONTACT MCR passive isolator, 2-channel, for the electrical isolation of..

MINI MCR-SL-2CP-I-I

2864655

PHOENIX_CONTACT

Available

Ship on today

MCR passive isolator, 2-channel, for the electrical isolation of current signals without auxiliary power, with screw connection

More details


Converters

INTERFACE Signal converters, switching devices, and power supply units - PHOENIX CONTACT

Modular Converter MCR technique. Analog - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$235.77
2+$230.16
3+$227.38
4+$226.49
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Width6.2 mm
Height93.1 mm
Depth102.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Degree of protectionIP20

Input data

Description of the inputCurrent input
Number of inputs2
Configurable/programmableno
Current input signal0 mA ... 20 mA
4 mA ... 20 mA
Max. input voltage18 V
Max. input current40 mA
Response currentapprox. 190 µA
Input voltage limitation< 2 V (20 mA)
Voltage dissipation1.7 V (I = 20 mA)

Output data

Output nameCurrent output
Number of outputs2
Configurable/programmableno
Current output signal0 mA ... 20 mA
4 mA ... 20 mA
Load/output load current output< 600 Ω (at I = 20 mA output signal)
Transmission Behavior1:1 to input signal

Power supply

Supply voltage rangeno separate supply voltage necessary

Connection data

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.12
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Stripping length12 mm
Screw threadM3

General

No. of channels2
Maximum transmission error≤ 0.1 % (of final value)
Maximum temperature coefficient≤ 0.002 %/K (of measured value / 100 Ω load)
Temperature coefficient, typical< 0.002 %/K (of measured value / 100 Ω load)
Additional error, load-dependent0.03 % (of measured value / 100 Ω load)
Limit frequency (3 dB)75 Hz
Step response (10-90%)5 ms (at 600 Ω load)
Electrical isolationBasic insulation according to EN 61010
Overvoltage categoryII
Degree of pollution2
Rated insulation voltage50 V AC/DC
Test voltage input/output1.5 kV (50 Hz, 1 min.)
Test voltage channel/channel1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Colorgreen
Housing materialPBT
Mounting positionany
Assembly instructionsThe T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
ConformanceCE-compliant
ATEX II 3 G Ex nA II T6 X
UL, USA / CanadaUL 508 Recognized
Class I, Div. 2, Groups A, B, C, D
GLGL EMC 2 D

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Evaluation criterionA
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Evaluation criterionB
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Evaluation criterionA

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Connection in acc. with standardCUL
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Evaluation criterionA
Standards/regulationsEN 61000-4-4
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Evaluation criterionA
Electrical isolationBasic insulation according to EN 61010
ConformanceCE-compliant
ATEX II 3 G Ex nA II T6 X
UL, USA / CanadaUL 508 Recognized
Class I, Div. 2, Groups A, B, C, D
GLGL EMC 2 D

[email protected]

[email protected] 4.027210120
[email protected] 4.127210120
[email protected] 5.027210120
[email protected] 5.127210120
[email protected] 6.027210120
[email protected] 7.027210120
[email protected] 8.027210120
[email protected] 9.027210120

ETIM

ETIM 2.0EC001485
ETIM 3.0EC001485
ETIM 4.0EC001485
ETIM 5.0EC002653

UNSPSC

UNSPSC 6.0130211506
UNSPSC 7.090139121008
UNSPSC 1139121008
UNSPSC 12.0139121008
UNSPSC 13.239121008

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2864655-MINI MCR-SL-2CP-I-IEnglish141 KbytesPHOENIX CONTACT-2864655-MINI MCR-SL-2CP-I-I

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or