MCR-FL-T-LP-I-EX 2864574 PHOENIX CONTACT MCR head-mounted temperature transducers: Programmable loop-powered.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MCR-FL-T-LP-I-EX 2864574 PHOENIX CONTACT MCR head-mounted temperature transducers: Programmable loop-powered..

MCR-FL-T-LP-I-EX

2864574

PHOENIX_CONTACT

Available

Ship on today

MCR head-mounted temperature transducers: Programmable loop-powered temperature transducers. Resistance thermometers, thermocouples, resistance-type sensors and voltage sensors.

More details


Programmable Logic Controllers Plcs

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$299.15
2+$292.47
3+$289.94
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Width12.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Degree of protectionIP20

Input data

Configurable/programmableYes, programmable
Sensor types (RTD) that can be usedPt, Ni (100, 500, 1000); min. measurement range 10 K
Sensor types that can be used (TC)B, C, D, E, J, K, L, N, R, S, T, U; min. measurement range 50 K/500 K
Connection method2, 3, 4-wire
Input signal range10 Ω ... 400 Ω (min. measurement range 10 Ω)
10 Ω ... 2000 Ω (min. measurement range 100 Ω)
-10 mV ... 100 mV (min. measurement range 5 mV)

Output data

Signal outputCurrent output
Current output signal4 mA ... 20 mA
20 mA ... 4 mA
Max. current output signal≤ 23 mA
Output current with short-circuit≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples)
Output current with wire break≤ 3.6 mA or ≥ 21 mA (adjustable)
Output current range with overrange/underrange3.8 mA ... 20.5 mA
Load/output load current output≤ 520 Ω (At UV = 24 V; Usupply - 12 V / 0.023 A)

Power supply

DesignationLoop-powered
Supply voltage range12 V DC ... 30 V DC
Max. current consumption< 3.5 mA

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length8 mm
Screw threadM3
Connection methodScrew connection
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

General

Step response (10-90%)< 2 s
Switch-on delay4 s
ConfigurationUsing MCR-PI-CONF-WIN configuration software package
Flammability rating according to UL 94V0
Standards/regulationsNAMUR recommendation NE 21
Housing materialPolyamide PA non-reinforced
Colorgreen
Line monitoringNE 43
ConformanceCE-compliant
ATEXEx II 2(1) G Ex ia IIC T4...T6
UL, USA / CanadacULus

Safety data

Max. output voltage Uo4.4 V DC
Max. output current Io9.6 mA
Max. output power Po10.6 mW
Max. ambient temperatureT4 = 85 °C, T5 = 65 °C, T6 = 50 °C
GroupIIA
Max. external inductivity Lo100 mH
Max. external capacity Co12 µF
GroupIIB
Max. external inductivity Lo100 mH
Max. external capacity Co12 µF
GroupIIC
Max. external inductivity Lo100 mH
Max. external capacity Co2.4 µF
Safety-related maximum voltage Um250 V

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2864574-MCR-FL-T-LP-I-EXEnglish127 KbytesPHOENIX CONTACT-2864574-MCR-FL-T-LP-I-EX

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or