MCR-FL-HT-T-I-EX 2864532 PHOENIX CONTACT MCR head-mounted temperature transducers, programmable, intrinsical.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MCR-FL-HT-T-I-EX 2864532 PHOENIX CONTACT MCR head-mounted temperature transducers, programmable, intrinsical..

MCR-FL-HT-T-I-EX

2864532

PHOENIX_CONTACT

Available

Ship on today

MCR head-mounted temperature transducers, programmable, intrinsically safe, for resistance thermometers, thermocouples, resistance-type sensors and voltage sensors. For Pt 100 resistance thermometers

More details


Programmable Logic Controllers Plcs

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$268.82
2+$262.64
3+$259.58
4+$259.50
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Ambient conditions

Degree of protectionIP00, IP66 (integrated in the connecting head)

Input data

Configurable/programmableYes, programmable
Sensor types (RTD) that can be usedPt, Ni (100, 500, 1000); min. measurement range 10 K
Sensor types that can be used (TC)B, C, D, E, J, K, L, N, R, S, T, U; min. measurement range 50 K/500 K
Connection method2, 3, 4-wire
Input signal range10 Ω ... 400 Ω (min. measurement range 10 Ω)
10 Ω ... 2000 Ω (min. measurement range 100 Ω)
-10 mV ... 100 mV (min. measurement range 5 mV)

Output data

Configurable/programmableYes, programmable
Current output signal4 mA ... 20 mA
20 mA ... 4 mA
Max. current output signal≤ 25 mA
Output current with short-circuit≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples)
Output current with wire break≤ 3.6 mA or ≥ 21 mA (adjustable)
Output current range with overrange/underrange3.8 mA ... 20.5 mA (linear increase/decrease)
Load/output load current output≤ 720 Ω (For UV = 24 V; Usupply - 8 V / 0.025 A)

Power supply

DesignationLoop-powered
Supply voltage range8 V DC ... 30 V DC
Max. current consumption< 3.5 mA

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.75 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.75 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.15
Stripping length8 mm
Screw threadM3
Connection methodScrew connection
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

General

Step response (10-90%)< 2 s
Switch-on delay6 s
ConfigurationUsing MCR-PI-CONF-WIN configuration software package
Flammability rating according to UL 94V0
Standards/regulationsNAMUR recommendation NE 21
Housing materialPolycarbonate, PC
Colorgreen
Line monitoringNE 43
ConformanceCE-compliant
ATEXEx II 1 G Ex ia IIC T6/T5/T4
UL, USA / CanadacULus

Safety data

Max. output voltage Uo8.2 V DC
Max. output current Io4.6 mA
Max. output power Po9.35 mW
Max. ambient temperatureCategory 1: T4 = 60°C, T5 = 50°C, T6 = 40°C
GroupIIB
Max. external inductivity Lo8.5 mH
Max. external capacity Co1.9 µF
GroupIIC
Max. external inductivity Lo4.5 mH
Max. external capacity Co974 nF
Safety-related maximum voltage Um250 V

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2864532-MCR-FL-HT-T-I-EXEnglish165 KbytesPHOENIX CONTACT-2864532-MCR-FL-HT-T-I-EX

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields