Inline intrinsically safe analog I/O terminal, 4 configurable input/output channels, complete with accessories

More details


AUTOMATION Industrial Automation - PHOENIX CONTACT

Control technology - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Width48.8 mm
Height136.8 mm
Depth71.5 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 70 °C
Permissible humidity (operation)10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20

General

Net weight222 g
Mounting typeDIN rail

Interfaces

Fieldbus systemLokalbus
DesignationInline local bus
Connection methodInline data jumper
Transmission speed500 kBit/s

Inline potentials

Supply for main circuit UEx28 V DC
Current consumption from UExmax. 187 mA
Communications power UL5 V DC (via voltage jumper)
Current consumption from ULmax. 50 mA

Analog inputs

Number of inputs4
Connection methodInline shield connector
2, 3-wire
Input nameAnalog inputs
Resolution A/D16 bit (15 bit + sign bit)
Type of protectionPolarity protection, surge protection
Data formatsIB IL, standardized represention, S7 compatible
Current input signal0 mA ... 20 mA
4 mA ... 20 mA
Voltage input signal0 V DC ... 10 V DC
0 V ... 10 V
Current input signal0 mA ... 20 mA
4 mA ... 20 mA

Analog outputs

Number of outputs4 (Can be configured as input or output)
Connection methodInline shield connector
2-wire
Type of protectionPolarity protection, surge protection
Data formatsIB IL, standardized represention, S7 compatible
Current output signal0 mA ... 20 mA
4 mA ... 20 mA
Load/output load current output500 Ω

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2869912-IB IL EX-IS AIO 4/EF-PACEnglish122 KbytesPHOENIX CONTACT-2869912-IB IL EX-IS AIO 4/EF-PAC

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or