ILB PB AI4 AO2 2878874 PHOENIX CONTACT Inline Block IO analog input/output module, PROFIBUS, inputs: 0-20 mA.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

ILB PB AI4 AO2 2878874 PHOENIX CONTACT Inline Block IO analog input/output module, PROFIBUS, inputs: 0-20 mA..

ILB PB AI4 AO2

2878874

PHOENIX_CONTACT

Available

Ship on today

Inline Block IO analog input/output module, PROFIBUS, inputs: 0-20 mA, 4-20 mA, ±20 mA, 0-5 V, ±5 V,0-10 V, ±10 V, Pt 100, Pt 1000, Ni 1000..., outputs: 0-5 V, ±5 V, 0-10 V, ±10V, 0-20 mA, ±20 mA, 4-20 mA, 2, 3, 4-conductor connection

More details


AUTOMATION Industrial Automation - PHOENIX CONTACT

I/O systems - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Product description

The multifunctional, analog Inline Block I/O modules can be used universally. The four inputs either offer the difference measured between analog current / voltage signals or the option of connecting resistance thermometers (RTDs). Furthermore, the current or voltage actuators can be connected at the two outputs. In addition, all channels are equipped with shield connections as a standard and are provided with the 2, 3 or 4-conductor system. The analog signals are made available with a resolution of 16 bits.

The plugs can be labeled using hinged labeling fields. The fields have insert cards that can be labeled individually to suit the application. Additionally, there is the proven ZBFM-6... Zack marker strip for labeling the terminal points.

Dimensions

Width156 mm
Height141 mm
Depth57 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 85 % (non-condensing)
Permissible humidity (storage/transport)10 % ... 95 % (non-condensing)
Air pressure (operation)80 kPa ... 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)66 kPa ... 108 kPa (up to 3500 m above mean sea level)
Degree of protectionIP20

General

Net weight465 g
Mounting typeDIN rail

Interfaces

Fieldbus systemPROFIBUS DP
DesignationInline local bus
Connection methodD-SUB-9 female connector
Transmission speed9,6 kBit/s ... 12 MBit/s
Transmission physicsCopper

Inline potentials

Communications power UL24 V DC
Power supply at ULmax. 8 A
Current consumption from ULtyp. 100 mA
max. 150 mA (AO-I nominal load)
Segment supply voltage US24 V DC
Power supply at USmax. 8 A
Current consumption from USmax. 220 mA (Maximum full load)

Analog inputs

Number of inputsmax. 4 (Differential inputs, voltage or current can be chosen separately)
Connection methodSpring-cage connection
2, 3, 4-wire (shielded)
Input nameAnalog inputs
A/D conversion timetyp. 180 µs
Resolution A/D16 bit
Limit frequency (3 dB)120 Hz (default for 4.5 ms filter)
450 Hz (for 1.1 ms filter)
Data formatsIB IL
Measured value resolution16 bits (15 bits + sign bit)
Current input signal0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Input resistance current inputtyp. 107 Ω
Voltage input signal-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Input resistance of voltage inputtyp. 276 kΩ
Number of inputs4 (differential inputs, voltage)
Type of protectionOverload protection, short-circuit protection of sensor supply
Open circuit responseGoes to 0 V
Voltage input signal0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Number of inputs4 (Differential inputs, current)
Type of protectionElectronic short-circuit protection
Open circuit responseGoing to 0 mA; open-circuit detection from 4 mA ... 20 mA
Current input signal0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Input resistance current inputtyp. 107 Ω
Number of inputs4
Input nameAnalog RTD inputs
Sensor types (RTD) that can be usedPt 100, Pt 500, Pt 1000, Ni 100, Ni 1000, Ni 1000 L&G
Linear resistance measuring range0 Ω ... 3200 Ω
0 Ω ... 9500 Ω
Protective circuitOverload protection, short-circuit protection of sensor supply

Analog outputs

Number of outputs2
Connection methodSpring-cage connection
2-wire (shielded)
Output nameAnalog outputs
D/A conversion timetyp. 70 µs
D/A resolution16 bit
Type of protectionShort-circuit protection of outputs
Data formatsIB IL
Representation of output values16 bits (15 bits + sign)
Process data update17 ms
Current output signal0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Load/output load current outputto 500 Ω
Voltage output signal0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Load/output load voltage output> 2 kΩ

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2878874-ILB PB AI4 AO2English139 KbytesPHOENIX CONTACT-2878874-ILB PB AI4 AO2

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or