UT 4-PE/L/HESI (5X20) 3214320 PHOENIX CONTACT Fuse modular terminal block, Connection method: Screw connecti.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

UT 4-PE/L/HESI (5X20) 3214320 PHOENIX CONTACT Fuse modular terminal block, Connection method: Screw connecti..

UT 4-PE/L/HESI (5X20)

3214320

PHOENIX_CONTACT

50

Available

Ship on today

Fuse modular terminal block, Connection method: Screw connection, Cross section: 0.14 mm²- 6 mm², AWG: 26 - 10, Nominal current: 28 A, Nominal voltage: 500 V, Width: 6.2 mm, Fuse type: G / 5 x 20, Fuse type: Glass, Mounting type: NS 35/7,5, NS 35/15, Color: black

More details


* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
50+$10.17
100+$10.04
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



General

NoteThe current is determined by the fuse used, the voltage by the selected LED.If the fuse is faulty, the downstream circuit will not be disconnected.
Number of levels3
Number of connections5
Nominal cross section4 mm²
Colorblack
Insulating materialPA
Flammability rating according to UL 94V0

General

FuseG / 5 x 20
Fuse typeGlass
Rated surge voltage6 kV
Pollution degree3
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipationmax. 1.6 W (With single arrangement of the fuse terminal block in the event of overload)
Connection in acc. with standardIEC 60947-7-2/IEC 60947-7-3
Maximum load current36 A (with 6 mm² conductor cross section)
Nominal current IN28 A (with 4 mm² conductor cross section)
Nominal voltage UN500 V
Connection in acc. with standardIEC 60947-7-3
Maximum load current (upper level)6.3 A (the current is determined by the fuse used)
Nominal current IN (upper level)6.3 A
Nominal voltage UN500 V (the voltage is determined by the fuse used)
Open side panelnein
Shock protection test specificationDIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protectionguaranteed
Finger protectionguaranteed
Oscillation, broadband noise test resultTest passed
Test specification, oscillation, broadband noiseDIN EN 50155 (VDE 0115-200):2008-03
Test spectrumService life test category 1, class B, body mounted
Test frequencyf1 = 5 Hz to f2 = 150 Hz
ASD level0.964 (m/s2)2/Hz
Acceleration0.58 g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
Shock test resultTest passed
Test specification, shock testDIN EN 50155 (VDE 0115-200):2008-03
Shock formHalf-sine
Acceleration5 g
Shock duration30 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Static insulating material application in cold-60 °C

Dimensions

Width6.2 mm
Length92.7 mm
Height NS 35/7,588.9 mm
Height NS 35/1596.4 mm

Connection data

NotePlease observe the current carrying capacity of the DIN rails.
Conductor cross section solid min.0.14 mm²
Conductor cross section solid max.6 mm²
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.6 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.10
Conductor cross section flexible, with ferrule without plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.4 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.4 mm²
2 conductors with same cross section, solid min.0.14 mm²
2 conductors with same cross section, solid max.1.5 mm²
2 conductors with same cross section, stranded min.0.14 mm²
2 conductors with same cross section, stranded max.1.5 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min.0.14 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max.1.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min.0.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max.1.5 mm²
Connection methodScrew connection
Stripping length9 mm
Internal cylindrical gageA4
Screw threadM3
Tightening torque, min0.6 Nm
Tightening torque max0.8 Nm

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-3214320-UT 4-PE/L/HESI (5X20)English135 KbytesPHOENIX CONTACT-3214320-UT 4-PE/L/HESI (5X20)