PSR-SCP- 24DC/TS/M 2986012 PHOENIX CONTACT Freely configurable safety module with 20 safe inputs and 4 safe .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PSR-SCP- 24DC/TS/M 2986012 PHOENIX CONTACT Freely configurable safety module with 20 safe inputs and 4 safe ..

PSR-SCP- 24DC/TS/M

2986012

PHOENIX_CONTACT

Available

Ship on today

Freely configurable safety module with 20 safe inputs and 4 safe outputs; 4 alarm, 2 clock, and 2 ground switching outputs; can be extended with additional I/O modules, up to SILCL 3, Cat.4/PL e, SIL 3, EN 50156, plug-in screw connection terminal blocks

More details


Programmable Logic Controllers Plcs

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Width67.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 55 °C
Ambient temperature (storage/transport)-20 °C ... 70 °C

Input data

Nominal input voltage UN24 V DC
Input voltage range in reference to UN0.85 ... 1.1
Typical input current at UN110 mA
Maximum response time< 30 ms
Bypassing voltage dips20 ms
Recovery time< 10 s
Protective circuitSurge protection Suppressor diode
Status display4 LEDs (green, red)
Number of safe inputs20
Nominal voltage UN24 V DC
Typical current consumption4 mA
Signal level "0" signal< 5 V
Signal level "1" signal> 11 V
Permissible cable length2000 m
Error detection time at 1-channel structure< 1 s

Output data

Contact type20 safe digital inputs
4 safe semiconductor outputs
4 alarm outputs
2 grounded switching outputs
4 clock outputs
Number of safe semiconductor outputs4 (Cat.4 / ISO 13849)
Number of ground switching outputs2
Nominal voltage UN24 V DC
Limiting continuous current2 A (see derating curve)
Max. capacitive load1 µF (When using electromechanical components (e.g., contactors), the capacitive load can be disregarded.)
Max. inductive loadA suitable and effective protective circuit is to be provided for inductive loads. A recommended measure is the use of free-wheeling diodes.
Test pulses< 1 ms (To ground)
Short-circuit protectionYes
Clock outputsYes
Number of outputs2
Nominal voltage UN24 V DC (A1 / A2)
Limiting continuous current100 mA
Test pulses~ 100 ms
Short-circuit protectionYes

General

Net weight430 g
Mounting typeDIN rail mounting
Degree of protectionIP54
IP20
Min. degree of protection of inst. locationIP54
Mounting positionHorizontal
Controlone and two channel
Parameters as per EN ISO 138494
Parameters for IEC 615083
Housing materialPolyamide PA non-reinforced
Number of possible safe extension modules10
InterfacesUSB

Connection data

Connection methodScrew connection
pluggableYes
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length7 mm
Screw threadM3

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2986012-PSR-SCP- 24DC/TS/MEnglish163 KbytesPHOENIX CONTACT-2986012-PSR-SCP- 24DC/TS/M