D-LAN-CAT.5-FP 2800723 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

D-LAN-CAT.5-FP 2800723 PHOENIX CONTACT Surge protection device

D-LAN-CAT.5-FP

2800723

PHOENIX_CONTACT

Surge protection device

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $130.52
Unit price: $130.52

Quantity Price
1+$130.52
2+$112.28
3+$103.88
4+$100.07
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2800723
Packing unit1 pc
Catalog pagePage 143 (C-4-2017)
GTIN4046356730273
Weight per Piece (excluding packing)90.000 g
Custom tariff number85363010
Country of originCN (China)

Dimensions

Height110 mm
Width28 mm
Depth60 mm (incl. NS 35 adapter)

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialABS
Flammability rating according to UL 94V0
Colorgray
Standards for cearances and creepage distancesIEC 60664
Mounting typeConnection-specific attachment plug and DIN rail, 35 mm
TypeAttachment plug for DIN rail mounting
Number of positions8
Direction of actionLine-Line & Line-Ground/Shield

Protective circuit

IEC test classificationB2
C1
VDE requirement classB2
C1
Maximum continuous voltage UC± 5 V DC
Maximum continuous voltage UC(wire-wire)± 5 V DC (± 57 V DC / PoE+)
Nominal current IN≤ 1.5 A (25 °C)
Operating effective current ICat UC≤ 600 µA
Nominal discharge current In(8/20) µs (line-line)350 A
Nominal discharge current In(8/20) µs (line-earth)350 A
Nominal pulse current Ian (10/700) µs (line-line)≤ 25 A
Nominal pulse current Ian (10/700) µs (line-earth)≤ 25 A
Output voltage limitation at 1 kV/µs (line-line) spike≤ 25 V
≤ 90 V (PoE)
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 750 V
Output voltage limitation at 1 kV/µs (line-line) static≤ 25 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 750 V
Residual voltage at In(line-line)≤ 35 V (C1 - 350 A)
≤ 110 V (C1 - 350 A)
Residual voltage at In(line-earth)≤ 700 V (C1 - 350 A)
Voltage protection level Up(line-line)≤ 20 V (B2 - 1 kV / 25 A)
≤ 90 V (B2 - 1 kV / 25 A - PoE)
≤ 35 V (C1 - 700 V/350 A)
≤ 110 V (C1 - 700 V/350 A - PoE)
Voltage protection level Up(line-earth)≤ 700 V (B2 - 1 kV / 25 A)
≤ 700 V (C1 - 700 V/350 A)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.≤ 1 dB (100 MHz/100 Ω)
Near-end crosstalk attenuation≤ 63.3 dB (1 MHz/100 Ω)
≤ 43.6 dB (16 MHz/100 Ω)
≤ 30.1 dB (100 MHz/100 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ohm system> 100 MHz
Capacity (line-line)typ. 15 pF (f= 1 MHz / VR= 0 V)
Capacity (line-earth)typ. 5 pF (f= 1 MHz / VR= 0 V)
Impulse durability (line-line)B2 - 1 kV / 25 A
C1 - 700 V / 350 A
Impulse durability (line-earth)B2 - 1 kV / 25 A
C1 - 700 V / 350 A

Connection data

Connection methodRJ45
Connection method INRJ45 socket
Connection method OUTRJ45 socket

Connection, equipotential bonding

Connection methodCable connection

Standards and Regulations

Standards/specificationsIEC 61643-21/A1 2008
GB/T 18802.21 2004
EN 61643-21/A1 2009

Environmental Product Compliance

REACh SVHCLead 7439-92-1

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.