UKH 50 3009118 PHOENIX CONTACT High-current terminal block, Connection method: Screw connection, Cross secti.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

UKH 50 3009118 PHOENIX CONTACT High-current terminal block, Connection method: Screw connection, Cross secti..

UKH 50

3009118

PHOENIX_CONTACT

Available

Ship tomorrow

High-current terminal block, Connection method: Screw connection, Cross section: 16 mm² - 70 mm², AWG: 6 - 2/0, Width: 20 mm, Height: 76 mm, Color: gray, Mounting type: NS 35/7,5, NS 35/15, NS 32, NS 35/15-2,3

More details


Core End Sleeves Cable Crimp

CLIPLINE 1 rail terminals - PHOENIX CONTACT

UT Universal Terminals – Screw connection terminal blocks - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$12.61
20+$10.60
39+$10.34
58+$10.22
78+$10.13
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



General

Number of levels1
Number of connections2
Nominal cross section50 mm²
Colorgray
Insulating materialPA
Flammability rating according to UL 94V0

General

Rated surge voltage8 kV
Pollution degree3
Overvoltage categoryIII
Insulating material groupI
Connection in acc. with standardIEC 60947-7-1
Maximum load current150 A (with 50 mm² conductor cross section)
Nominal current IN150 A
Nominal voltage UN1000 V
Open side panelnein
Shock protection test specificationDIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protectionguaranteed
Finger protectionguaranteed
Result of surge voltage testTest passed
Surge voltage test setpoint9.8 kV
Result of power-frequency withstand voltage testTest passed
Power frequency withstand voltage setpoint2.2 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)Test passed
Result of bending testTest passed
Bending test rotation speed10 rpm
Bending test turns135
Bending test conductor cross section/weight25 mm² / 4.5 kg
50 mm² / 9.5 kg
70 mm²/10.4 kg
Tensile test resultTest passed
Conductor cross section tensile test25 mm²
Tractive force setpoint135 N
Conductor cross section tensile test50 mm²
Tractive force setpoint236 N
Conductor cross section tensile test70 mm²
Tractive force setpoint285 N
Result of tight fit on supportTest passed
Tight fit on carrierNS 32/NS 35
Setpoint10 N
Result of voltage-drop testTest passed
Requirements, voltage drop≤ 3.2 mV
Result of temperature-rise testTest passed
Short circuit stability resultTest passed
Conductor cross section short circuit testing50 mm²
Short-time current6 kA
Result of thermal testTest passed
Proof of thermal characteristics (needle flame) effective duration30 s
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Static insulating material application in cold-60 °C

Dimensions

Width20 mm
Length70.5 mm
Height76 mm
Height NS 35/1583.5 mm
Height NS 3281 mm

Connection data

Connection methodScrew connection
Connection in acc. with standardIEC 60947-7-1
NoteNote: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
Conductor cross section solid min.16 mm²
Conductor cross section solid max.70 mm²
Conductor cross section AWG min.6
Conductor cross section AWG max.2/0
Conductor cross section flexible min.25 mm²
Conductor cross section flexible max.70 mm²
Min. AWG conductor cross section, flexible3
Max. AWG conductor cross section, flexible2/0
Conductor cross section flexible, with ferrule without plastic sleeve min.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.50 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.50 mm²
2 conductors with same cross section, solid min.10 mm²
2 conductors with same cross section, solid max.16 mm²
2 conductors with same cross section, stranded min.10 mm²
2 conductors with same cross section, stranded max.16 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min.10 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max.16 mm²
Connection in acc. with standardIEC/EN 60079‑7
Conductor cross section solid min.16 mm²
Conductor cross section solid max.50 mm²
Conductor cross section AWG min.6
Conductor cross section AWG max.1/0
Conductor cross section flexible min.25 mm²
Conductor cross section flexible max.50 mm²
Stripping length24 mm
Internal cylindrical gageB10
Screw threadM6
Tightening torque, min6 Nm
Tightening torque max8 Nm

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-3009118-UKH 50English128 KbytesPHOENIX CONTACT-3009118-UKH 50

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields