PI-EX-SD-24-48 2865298 PHOENIX CONTACT Ex-i solenoid driver, pluggable. To control intrinsically safe soleno.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PI-EX-SD-24-48 2865298 PHOENIX CONTACT Ex-i solenoid driver, pluggable. To control intrinsically safe soleno..

PI-EX-SD-24-48

2865298

PHOENIX_CONTACT

Available

Ship on today

Ex-i solenoid driver, pluggable. To control intrinsically safe solenoid valves, alarm modules as well as simple electric equipment installed in Ex areas. For Group IIC gases, loop-powered. Electrical isolation.

More details


Programmable Logic Controllers Plcs

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$165.69
2+$161.36
3+$159.22
4+$157.86
5+$156.94
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Width12.4 mm
Height145 mm
Depth147 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 55 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (relative humidity, non-condensing)
Degree of protectionIP20

Output data

Output characteristic curve: Output resistor≤ 278 Ω (Internal resistance Ri)
Response time< 30 ms

Compatible valves

NoteThis is an extract of possible combinations of valves and solenoid drivers.
Compatible valveASCO Coil 195
ASCO Coil 302 (12 V)
Bürkert Coil AC 10 standard
Bürkert Coil AC 10 high resistance
Bürkert Coil AC 21 standard 700 mW / 65°C
Bürkert Coil AC 21 high resistance 700 mW / 65°C
Bürkert Coil AC 21 standard 900 mW / 45°C
Bürkert Coil AC 21 high resistance 900 mW / 45°C
Bürkert Coil AC 21 standard 900 mW / 60°C
Bürkert Coil AC 21 high resistance 900 mW / 60°C
Bürkert Coil G1 642735 standard 800 mW / 40°C
Bürkert Coil G1 642735 high resistance 800 mW / 40°C
Bürkert Coil G1 642735 standard 1000 mW / 40°C
Bürkert Coil G1 642735 high resistance 1000 mW / 40°C
FESTO Coil MFH-...IA-SA-EX GBXE022AIAD03
FESTO Coil (J)MFH-...BIA-SA-EX GBXE022AIAD03
Norgren Herion Coil 2050
Norgren Herion Coil 2051
Norgren Herion Coil 2052
Norgren Herion Coil 2053
Norgren Herion Coil 2080 / 2082
Norgren Herion Coil 2081 / 2083
Norgren Herion Coil 2084
Norgren Herion Coil 3039
Nass Coil 1259 30.1-00
Nass Coil 1259 50.1-00
Parker Coil VZ07 488650.01
Parker Coil VZ33 494035.10
Parker Coil VZ08 488660.01
Parker Coil VZ09 488670.01
Parker Coil VZ95 482160.01 EEx ia IIB T6
Parker Coil VZ23 482870.01
Samson Coil 3701-12 (12 V)
Samson Coil 3701-13 (24 V)
Samson Coil 3963-12 (12 V)
Samson Coil 3963-13 (24 V)
Samson Coil 3964-12 (12 V)
Samson Coil 3964-13 (24 V)
Seitz Pilot valve PV 12F73 Ci oH
Seitz Pilot valve PV 12F73 Xi oH
Seitz Pilot valve PV 12F73 Xi oH-2
Seitz Solenoid coil 11 G 52

Power supply

Max. current consumption< 110 mA (at 24 V)
Power consumptionmax. 1.5 W (at 24 V)

General

Maximum temperature coefficient0.01 %/K
Status displayYellow LED (status display)
Red LED (line errors)
Flammability rating according to UL 94V0
Housing materialPBT and polyamide PA non-reinforced
Colorgreen
DesignationInput/output
Electrical isolation375 V (Peak value as per EN 50020 / EN 60079-11)
2.5 kV (50 Hz, 1 min., test voltage)
ConformanceCE-compliant
ATEXEx II (1) GD [Ex ia] IIC / IIB / IIA
Ex II 3 G Ex nA II T4 X
Functional Safety (SIL)SIL 3

Safety characteristic data

Integrity requirementIEC 61508 - Low demand
Equipment typeType A
Safety Integrity Level (SIL)3
Safe Failure Fraction (SFF)100 %
λSU2.84 x 10-7 (284 FIT)
λSD0
λDU0
λDD0
Probability of a hazardous failure on demand (PFDAVG)0 (1 year)
0 (5 years)
0 (10 years)
Diagnostic coverage (DC)DCS = 0%, DCD = 0%

Safety data

Max. output voltage Uo27.7 V
Max. output current Io101 mA
Max. output power Po697 mW
GroupIIA
Max. external inductivity Lo20 mH
Max. external capacity Co0.44 µF
GroupIIB
Max. external inductivity Lo2 mH
Max. external capacity Co0.29 µF
GroupIIC
Max. external inductivity Lo0.5 mH
Max. external capacity Co0.067 µF
Max. ratio Lo/Ro51.1 µH/Ω
Additional textPlease follow the technical data regarding the connecting cables used.
Safety-related maximum voltage Um250 V AC (125 V DC)

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2865298-PI-EX-SD-24-48English153 KbytesPHOENIX CONTACT-2865298-PI-EX-SD-24-48

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or