EEM-MA400 2901364 PHOENIX CONTACT Energy measurement device to measure electrical parameters in low voltage .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

EEM-MA400 2901364 PHOENIX CONTACT Energy measurement device to measure electrical parameters in low voltage ..

EEM-MA400

2901364

PHOENIX_CONTACT

Available

Ship on today

Energy measurement device to measure electrical parameters in low voltage installations up to 500 V, acquisition of total harmonic oscillations - can be extended with RS-485 communication module

More details


Energy Meters Control Analizers

INTERFACE Signal converters, switching devices, and power supply units - PHOENIX CONTACT

Energy meters. Monitoring - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$321.25
2+$314.23
3+$312.24
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Width96 mm
Height96 mm
Depth82 mm
Installation depth with extension module80 mm
Installation depth without extension module60 mm

Ambient conditions

Degree of protectionIP52 (front), IP30 (back)
Ambient temperature (operation)-10 °C ... 55 °C (14 °F to 131 °F)
Ambient temperature (storage/transport)-20 °C ... 85 °C (-4 °F ... 185 °F)
Max. permissible relative humidity (operation)≤ 95 %
Max. salt spray content≤ 2.5 %
Altitude≤ 2000 m
Ambient temperature (operation)0 °C ... 40 °C
Max. permissible relative humidity (operation)80 % (up to 31°C)
50 % (at 40 °C)

Input data

Measuring principleTrue r.m.s. value measurement
Acquisition of harmonicsup to 51st harmonic
Measured valueAC sine (50/60 Hz)
Input nameVoltage measuring input V1, V2, V3
Input voltage range50 V AC ... 500 V AC (Phase/Phase)
28 V AC ... 289 V AC (Phase/neutral conductor)
Precision0.2 %
Input current rangeVia external transformers
Input current9999 A (primary)
5 A (secondary)
Current measuring range0 kA ... 11 kA
Overload capacity6 A (Permanent)
Response threshold from measuring range nominal value5 mA
Precision0.2 %
Current overload10 x IN for 1 s
Messbereich_Leistung0 MW ... 11 MW
0 Mvar ... 11 Mvar
0 MVA ... 11 MVA
Precision0.5 %
Active energy (IEC 62053-22)Class 0.5 S
Reactive power (IEC 62053-23)Class 2

Output data

Output descriptionVia function module

Interfaces

DesignationVia communication module

General

DisplayLCD display, backlighting
Measuring rateapproximately
Supply voltage range110 V AC ... 400 V AC ±10 %
Nominal power consumption5 VA
Power consumption10 VA (With maximum number of extension modules)
Mains type3-phase (3 or 4-wire), 2-phase (2-wire), and single-phase (1-wire)
Colorblack
ConformanceCE-compliant
Rated insulation voltage300 V AC (EN 61010-1)
Overvoltage categoryIII
Test voltage3.5 kV AC (50 Hz, 1 min.)
2.2 kV AC (50 Hz, 1 min.)

Connection data

Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section solid min.0.5 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section AWG min.20
Conductor cross section AWG max.14
Connection methodCOMBICON plug-in screw terminal block
Stripping length6 mm
Tightening torque0.4 Nm
NoteVoltage and other connections
Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.6 mm²
Conductor cross section solid min.0.5 mm²
Conductor cross section solid max.6 mm²
Conductor cross section AWG min.20
Conductor cross section AWG max.8
Connection methodScrew connection
Stripping length7 mm
NoteCurrent connection

UL data

Nominal supply voltage range110 V AC ... 240 V AC ±10 %
120 V DC ... 250 V DC ±10 %
Power consumption10 VA
Operating modeIndoor use
Surge voltagesTransient overvoltage according to installation classes
Overvoltage categoryI, II, III
Overvoltage category of the supplyMin. II

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2901364-EEM-MA400English111 KbytesPHOENIX CONTACT-2901364-EEM-MA400

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or