HC-M-HS-MOD-ST 1605000 PHOENIX CONTACT HEAVYCON contact insert module, male, 2-pos. to 100 A, screw connecti.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

HC-M-HS-MOD-ST 1605000 PHOENIX CONTACT HEAVYCON contact insert module, male, 2-pos. to 100 A, screw connecti..

HC-M-HS-MOD-ST

1605000

PHOENIX_CONTACT

Available

Ship on today

HEAVYCON contact insert module, male, 2-pos. to 100 A, screw connection

More details


Core End Sleeves Cable Crimp

PLUSCON Field cabling - PHOENIX CONTACT

Heavy industrial connectors - PLUSCON heavy - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$37.34
6+$34.14
12+$33.30
18+$32.88
24+$32.61
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Electrical characteristics

NoteFor HEAVYCON HC-B6 to B48 housing (housing height: min. 72 mm), HC-M-MHR... hinged retaining frame required, axial connection for 4 mm Allen key
Rated voltage (III/3)1000 V
Rated current100 A
Rated surge voltage8 kV
Number of positions2

Ambient conditions

Ambient temperature (operation)-40 °C ... 125 °C

Mechanical characteristics

Conductor cross section16 mm² ... 35 mm² (The cross section specification refers to the geometric cross section of the cable used)
Connection cross section AWG4 ... 2
Stripping length of the individual wire13 mm
Tightening torque6 Nm (16 mm²)
7 Nm (25 mm²)
8 Nm (35 mm²)
Wire diameter including insulation11.4 mm
Hexagonal socketSW 4
Insertion/withdrawal cycles≥ 500
Minimum housing height72 mm

General

SeriesHC-M-HS
Number of module slots2
Connection methodAxial screw connection
Flammability rating according to UL 94V0
Pollution degree3
Overvoltage categoryIII
Assembly instructions- Use HC housing h >= 72 mm- Connection of wires using a 4 mm Allen wrench- Axial screw connection only for stranded wires- Plug-in connections may only be operated only when there is no load/voltage
ConnectionNote for axial connection method The specified conductor cross sections refer to the geometric cross section of the used conductor.The use of conductors with a geometric cross section that deviates greatly from the nominal cross section of the conductor should be checked first.The wiring space of the axial screw technology has been designed for fine strand conductors as per VDE 0295 class 5. Deviating conductor superstructures (e.g. class 6 conductors) must be checked before use.Connection It must be ensured before installation that the ball screw is completely turned back (chamber is open). Twisting the conductors is not allowed. The cores must be pushed up to the end of the contact chamber (until the contact is insulated). Keep the core in this position and tighten it using an Allen key. The required core end must be cut before a reconnection. Tightening the connection screw is allowed only once in order to prevent a breakage of the litz wire.

Material data

Contact materialCopper alloy
Contact surface materialAg
Contact carrier materialPC

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-1605000-HC-M-HS-MOD-STEnglish124 KbytesPHOENIX CONTACT-1605000-HC-M-HS-MOD-ST

Reviews (0)

No customer reviews for the moment.