MINI MCR-2-POT-UI 2902016 PHOENIX CONTACT Resistance/potiposition transducer View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MINI MCR-2-POT-UI 2902016 PHOENIX CONTACT Resistance/potiposition transducer

MINI MCR-2-POT-UI

2902016

PHOENIX_CONTACT

Resistance/potiposition transducer

More details


INTERFACE Components (IF)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $278.82
Unit price: $278.82

Quantity Price
1+$278.82
2+$265.72
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2902016
Packing unit1 pc
Catalog pagePage 88 (C-5-2017)
GTIN4046356649551
Weight per Piece (excluding packing)110.000 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width6.2 mm
Height110.5 mm
Depth120.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C

Input data

Potentiometer100 Ω ... 100 kΩ

Output data

Voltage output signal1 V ... 5 V (via DIP switch)
10 V ... 0 V (via DIP switch)
0 V ... 5 V (via DIP switch)
0 V ... 10 V (via DIP switch)
0 V ... 10.5 V (can be set via software)
Current output signal0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
20 mA ... 0 mA (via DIP switch)
20 mA ... 4 mA (via DIP switch)
0 mA ... 21 mA (can be set via software)
Max. voltage output signalapprox. 12.3 V
Max. current output signal24.6 mA
Load/output load voltage output≥ 10 kΩ
Load/output load current output≤ 600 Ω (at 20 mA)

Power supply

Supply voltage24 V DC
9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Current consumption33 mA (24 V DC)
68 mA (12 V DC)

Connection data

Single conductor/terminal point, solid, with ferrule, min.0.2 mm²
Single conductor/terminal point, solid, with ferrule, max.1.5 mm²
Single conductor/terminal point, solid, without ferrule, min.0.2 mm²
Single conductor/terminal point, solid, without ferrule, max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Min. AWG conductor cross section, flexible24
Max. AWG conductor cross section, flexible12
Stripping length10 mm
Screw threadM3
Connection methodScrew connection

General

Maximum transmission error< 0.1 % (R < 240 Ω = < 0,2 %)
Maximum temperature coefficient0.01 %/K
Temperature coefficient, typical0.01 %/K
Step response (10-90%)< 60 ms
Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Housing materialPBT
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value0.2 %
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value0.4 %
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value0.2 %

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Standards/regulationsEN 61000-4-2
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
EN 61000-4-4
EN 61000-4-5
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Electrical isolationReinforced insulation in accordance with IEC 61010-1
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T5
Class I, Zone 2, Group IIC T5
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.